M5D

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-2475  P. 2 / 2

TERMINAL CONNECTIONS

Connect the unit as in the diagram below or refer to the 
connection diagram on the front of the unit.

 

EXTERNAL DIMENSIONS  unit: mm (inch)

94 (3.70)

3 (.12)

25 (.98)

41 (1.61)

[3.3 (.13)]

• When mounting, no extra space is needed between units.

DIN RAIL

35mm wide

8–M3.5 SCREW

7.3 (.29)

1 2

3 4

5 6

7 8

 

CONNECTION DIAGRAM

5

6

1

2

4

3

*

  Use either output 1 or output 2.

    Shortcircuit the unused output.

**

 Be sure to match specifications of smart transmitter

     when using output 2.

7

8

+

POWER

OUTPUT 1

+

OUTPUT 2

+

*

**

2-WIRE

TRANSMITTER

WIRING INSTRUCTIONS

 

SCREW TERMINAL 

Torque: 0.8 N·m

CHECKING

1) Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2) Power input voltage:  Check voltage across the terminal 

7 – 8 with a multimeter.

3) Input:  Check that the input signal is within 0 – 100% of 

the full-scale.

4) Output:  Check that the load resistance meets the de-

scribed specifications.

LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protector for 
protection against induced lightning surges.  Please contact 
M-System to choose appropriate models.