DL30-G USERS MANUAL EM-8571-G Rev.2
Resetting totalized value (PI)
The cumulative total value of a specific PI can be reset at the timing of zone transition.
The PI channel to be operated needs to be assigned in advance.
➔
(1) Click [Alarm zone setting] button in the [PI setting] to display the [PI Alarm zone setting]. Click [Reset
totalized value (PI)] button in a specific zone to display the [Reset totalized value].
PI setting
PI alarm zone setting
1. Click
Reset totalized value (PI)
2. Click
(2) Double-click the PI channel to be operated and set as Disable/Enable.
1. Double-click
2. Select
4. Click
3. Click
Reset totalized value (PI)
(3) Click [Back] to return to the [PI Alarm zone setting] window.