BEFORE USE ....

Thank you for choosing M-System.  Before use, check the package 
you received as below.
If you have any problems or questions with the product, please 
contact M-System's Sales Office or representatives.

PACKAGE INCLUDES:

  Signal conditioner (body + base input resistor).....(1)
  Input resistor is provided only with current input type.

MODEL NO.

Check that model No. described on specification label is exactly 
what you ordered.

INSTRUCTION MANUAL

This manual describes necessary points of caution when you 
use this product, installation, connection and basic maintenance 
procedures.

COMPONENT IDENTIFICATION

Body

Base Socket

Specification

 Label

x10

HI SET.

(%)

X1

  x10

LO SET.

(%)

 X1

12

3

4

5

6 7

890

12

34

5

67

8 9

0

12

3

4

5

67

89

0

12

34

5

67

89 0

DC ALARM

(rotary switch adjustment)

MODEL

ASWL2

INSTRUCTION  MANUAL

INSTALLATION

Detach the yellow clamps located at the top and bottom of the 
unit for separating the body from the base socket.

DIN RAIL MOUNTING

Set the base socket so that its 
DIN rail adaptor is at the bot-
tom.  Position the upper hook at 
the rear side of 
base socket on the DIN rail and 
push in the lower.  When remov-
ing the socket, push down the 
DIN rail
adaptor utilizing a screwdriver 
(–) and pull.

WALL MOUNTING

Refer to “EXTERNAL DIMEN-
SIONS.”

Clamp

(top & bottom)

DIN Rail

35mm wide

Spring Loaded

DIN Rail Adaptor

Shape and size of the base socket 
are slightly different with various 
socket types.

POINTS OF CAUTION

n

 CONFORMITY WITH EC DIRECTIVES

• This equipment is suitable for Pollution Degree 2 and  Instal

-

lation Category II.  

  The relay output circuit is suitable for use in Pollution Degree 

2 environment in Over Voltage Category II with the maximum 
operating voltage 150V, in Over Voltage Category I with 240V.

  Reinforced insulation (signal input or output to power input:  

300V) and basic insulation (signal input to output: 300V) are 

maintained.  Prior to installation, check that the insulation 
class of this unit satisfies the system requirements.

• The equipment must be mounted inside a suitable fire enclosure. 
• Altitude up to 2000 meters
• The equipment must be installed such that appropriate clear

-

ance and creepage distances are maintained to conform to CE 
requirements.  Failure to observe these requirements may 
invalidate the CE conformance. 

n

 POWER INPUT RATINGS

•  Operational  range  &  power  consumption:  Check  the  power 

rating for the unit on the specification label.

    AC rating: Rating ±10%, 50/60 ±2 Hz, approx. 2VA
    DC rating: Rating ±10%, approx. 2W

GENERAL

• Before you remove the unit from its base socket or mount it, 

turn off the power supply and input signal for safety.

ENVIRONMENT

• Indoor use.
• When  heavy  dust  or  metal  particles  are  present  in  the  air, 

install the unit inside proper housing and ventilate it.

•  Do  not  install  the  unit  where  it  is  subjected  to  continuous 

vibration.  Do not apply physical impact to the unit.

• Environmental temperature must be within -5 to +60°C (23 

to 140°F) with relative humidity within 30 – 90% RH in order 

to ensure adequate life span and operation.

Input Resistor

WIRING

• Do not install cables (power supply, input and output) close 

to noise sources (relay drive cable, high frequency line, etc.).

• Do not bind these cables together with those in which noises 

are present.  Do not install them in the same duct.

AND ....

• The unit is designed to function as soon as power is supplied, 

however, a warm up for 10 minutes is required for satisfying 
complete performance described in the data sheet.