AS4M
P. 3 / 4
EM-1605 Rev.11
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
TERMINAL CONNECTIONS
Connect the unit as in the diagram below or refer to the con-
nection diagram on top of the unit.
U(+)
V(–)
POWER
7
8
10
11
9
2
3
1
L2 OUTPUT
L1 OUTPUT
N.C.
N.O.
COM
N.C.
N.O.
COM
■
SPDT RELAY
U(+)
V(–)
POWER
7
8
10
11
9
2
3
1
L4 OUTPUT
L1 OUTPUT
COM
L3 OUTPUT
L2 OUTPUT
COM
■
N.O. RELAY
■
N.C. RELAY
10
11
9
2
3
1
L4 OUTPUT
L1 OUTPUT
COM
L3 OUTPUT
L2 OUTPUT
COM
4
5
6
4
5
6
+
–
3
2
1
POTENTIOMETER
max.
min.
+
–
3
2
1
POTENTIOMETER
max.
min.
CHECKING
1) Terminal wiring: Check that all cables are correctly con-
nected according to the connection diagram.
2) Power input voltage: Check voltage across the terminal
7 – 8 with a multimeter.
3) Input: Check voltage across the terminal 5 (+) – 6 (–)
with a voltmeter to show 0V at 0% potentiometer input
and the same voltage as that across 4 (+) – 6 (–) at 100%
input.
4) Alarm operations: Check the alarm operations referring
to the figure below.
5) Output load: Check that the output load is 380V
AC/120VA or 125V DC/30W (380V AC/600VA or 125V
DC/150W for dual alarm, Output Code 5) at the maxi
-
mum. For maximum relay life with inductive load, ex-
ternal protection is recommended.
0
50
100
Input
(%)
LL
L
HH
H
L2 (1–2)
ON
L3 (1–3)
ON
L4 (9–11)
ON
OFF
OFF
L1 (9–10)
ON
OFF
OFF
Alarm Trip Operation
Terminal No. in parentheses
Example with quad N.O. contacts (LL, L, H, HH)
Trip Operation in Power Failure
• Output code 2: All relays turn off.
• Output code 3: All relays turn on.
• Output code 5: Terminals 1 – 3, 9 – 11 turn on.
ITEM
MDF.
DATA
CONTENTS
DEFAULT SETTING
CODE
27
2
0.0 – 100.0
0% input (%) (ITEM 27 < ITEM 28)
0.0
28
2
0.0 – 100.0
100% input (%) (ITEM 27 < ITEM 28)
100.0
29
2
0, 1
Latching control
(0: Disabled, 1: Enabled)
0
Selecting “0” resets latching relays. Turning power supply off
also resets them.
30
----
0000 – 1111
Alarm indication
(0: OFF, 1: ON)
----
The MSD indicates the L1, while the LSD indicates the L4.
*1. Selectable within the display scaling range
*2. Quad alarm trip type only
*3. Of the range set in ITEM 05/06. ITEM 07 < ITEM 08.