60
73ET/74ET/75ET USERS MANUAL EM-7353-0003B Rev.5
For discrete inputs, assign 16 channels when 1 data area is assigned. For 4 or 8 data areas, 64 channels are
automatically assigned. Module 9 and later modules’ settings are identical to Module 8 setting.
Table 7.2.3b: R3 discrete channel assignment example.
CAUTION !
For use of Discrete Output Modules (model: R3-DCxx) with the 74ET and 75ET, there are limitations in their mount-
ing positions with the 10-position (model: R3-BS10), 12-position (model: R3-BS12), 14-position (model: R3-BS14)
and the 16-position (R3-BS16) bases.
With the data allocation mode 1, the R3-DCxx must be positioned between Module 1 through 8. DO NOT use
Module 9 and later modules’ for the R3-DCxx.
With the data allocation mode 4, 8 and 16, the R3-DCxx must be positioned at Module 1 and/or 2.
CAUTION !
For Trigger recording, Channel 1 of each R3 nodes is automatically used as trigger input. Install an discrete input
module at Module 1 position and set the trigger input channel to 1.
Input Type
Specify ‘0 to 100 percent’ for voltage input, or type of temperature sensor for thermocouple/RTD input.
Discrete setting is the same as for the R1M.
Table 7.2.3c: Input types for R3.
SLOT NO.
DATA AREA
CHANNEL NO.
I/O 1
4
1 through 64
I/O 2
1
65 through 80
I/O 3
1
81 through 96
I/O 4
1
97 through 112
MODEL
I/O TYPE
SELECTIONS
USABLE RANGE
NOTES
°
C
°
F
R3-TSxx
Thermocouple input
(PR)
0 – 1760
-62 – 3200
K (CA)
-270 – 1370
-454 – 2498
E (CRC)
-270 – 1000
-454 – 1832
J (IC)
-210 – 1200
-346 – 2192
T (CC)
-270 – 400
-454 – 752
B (RH)
100 – 1820
212 – 3308
R
-50 – 1768
-58 – 3214
S
-50 – 1768
-58 – 3214
C (WRe 5-26)
0 – 2315
32 – 4199
N
-270 – 1300
-454 – 2372
U
-200 – 600
-328 – 1112
L
-200 – 900
-328 – 1652
P (Platinel II)
0 – 1395
32 – 2543
R3-RSxx
RTD input
Pt 100 (JIS ’97/DIN/IEC)
-200 – 850
-328 – 1562
Pt 100 (JIS ’89)
-200 – 660
-328 – 1220
JPt 100 (JIS ’89)
-200 – 510
-328 – 950
Pt 50
Ω
(JIS ’81)
-200 – 649
-328 – 1200
Ni 100
-80 – 250
-112 – 482
Cu 10
-50 – 250
-58 – 482
Pt 1000*
-200 to 850
-328 to 1562
Ni 508.4*
-50 – 200
-58 – 392
Cu 50
-235 – 560
-391 – 1040
Ni 1000*
-56 to 152
-68 to 305
MODEL
I/O TYPE
SELECTIONS
INPUT RANGE
NOTES
R3-SVxx
DC voltage input
R3-DSxx
4 – 20mA input with excitation
R3-SSxx
DC current input
0 to 100 percent
0 – 100%
R3-CTxx
CT input
R3-PTxx
PT input
R3-DAx
Discrete input, 16 or 32 points
R3-DCx
Discrete output, 16 or 32 points
*Not usable for R3-RS8x.
Содержание 75ET