73ET/74ET/75ET USERS MANUAL EM-7353-0003B Rev.5
Overview Color
Specify the bargraph color for the pen in the Overview. Use the color palette.
3.17.3 PEN SETTING (ANALOG ALARM)
Touch Pen Setting (Analog Alarm) button on the Setting view or Alarm button on Pen Setting (Common) view for a
specific pen to configure alarm setting on the Pen Setting (Analog Alarm) view (Figure 3.17.3).
Figure 3.17.3: Pen setting (analog alarm).
This option can be changed while recording.
Alarm Setpoint
Specify Lower and Upper setpoints in engineering unit within the Engineering Range, using numeric keypad.
Alarm Deadband
Alarms are reset when the signal goes out of the alarm zone by the deadband values specified for each alarm
setpoint.
Alarm Output
Alarm contact outputs can be provided to external output devices. Specify ‘Enable’ to activate the contact outputs.
Node & Channel Number
Touch the data fields below each Alarm Output field and specify Node Number and Channel Number of the output
module.
For using the built-in contact output for models R1MS-GH3, R2M-2H3 and R2M-2G3, specify ‘Channel 1.’
Normal & Alarm Color
Colors specified for normal and alarm conditions are used for digital indicator values on the Record view.
Use the color palette.
Alarm Message
Touch the data fields below each Alarm Output field and specify messages to represent the upper and lower alarms
on the Overview or on the Alarm History view. Use the alphanumeric keypad. Max. 10 characters.