7xETBLD USERS MANUAL EM-7353-0003C
2.4
SETTING ON THE 7xETBLD
2.4.1 COMMUNICATION SETTING
DEMO:
You can run the 7xET program without actual signal input for learning, evaluation and demonstra-
tion when you choose DEMO.
RxM:
Choose this option when you connect R1M/R2M via Modbus RTU.
IP address:
Enter 7xET’s static IP address. 192.168.0.1 entered in the field upon the first startup is M-Sys-
tem’s ex-factory setting.
2.4.2 STORING RATE
Choose among 0.5 sec., 1 sec., 2 sec., 5 sec., 10 sec., 1 min., and 10 min.
2.4.3 DATA STORING METHOD
There are four (4) storing modes as explained below:
No storing:
Sampled data are plotted on the screen but no recording is executed.
Normal:
Recording is manually initiated and stopped. Data is continuously stored while the recording is on.
Trigger (A):
Remote trigger. Data is automatically recorded while the external trigger condition (input) is true.
Trigger (B):
Event Recording. The 7xET detects an external event by trigger signal, and stores preset number
of samples before and after the moment of event.
Auto:
Recording is automatically initiated and stopped at a predefined time.
Trigger (A), remote trigger mode setting
Remote trigger mode is applicable only to the R1M or R2M series I/O modules.
Data is automatically recorded while the external trigger condition (input) is true.
Condition:
Specify whether the recorder should identify On or Off of the contact signal as trigger condi-
tion. For example, when the Condition is set to On, the 7xET stores data while the signal is On
and stops recording when it is turned to Off.
Node Number:
Specify which R1M/R2M device connected to the 7xET is used to trigger. Enter numbers and
alphabets on the alphanumeric keypad which opens by pressing the current selection.
Trigger (B), event recording mode setting
Event recording mode is applicable only to the R1M or R2M series I/O modules.
Recording is automatically initiated according to predetermined trigger conditions and preset number of samples
before and after the moment of event are stored.
Rise or Sink:
Specify whether the recorder should identify a rise or sink of the contact signal as trigger.
Node number:
Specify which R1M/R2M device connected to the PC is used to trigger.
Pretrigger / Posttrigger: 1200 samples at the maximum for each can be stored. Specify numbers of samples to
be stored before (Pretrigger) and after (Posttrigger) the event respectively.
Pretrigger recording is applicable only when the storing rate is set to 0.5 or 1 sec.
Auto store setting
Either ‘One time only’ or ‘Every day’ option can be selected.
When you choose ‘One time only’ option, data is stored once at a predefined time. With ‘Every day’ option, the 7xET
runs recording once per day at a predefined time.
Specify time and duration of a recording cycle, including a date for ‘One time only’ recording. For ‘Every day’
recording, you do not need to specify ‘Year,’ ‘Month’ or ‘Day.’
2.4.4 START MODE
Cold Start:
At a restart, the 7xET stands by showing the initial view.
Hot Start:
At a restart, the 7xET automatically starts recording.
2.4.5 TEMPERATURE UNIT
Choose either
°
C (Celsius) or
°
F (Fahrenheit).