98
47DT OPERATING MANUAL EM-9508-B Rev.7
10.7 ONE-SHOT OUTPUT
Alarm outputs can be provided as one-shot pulses. The one-shot output can be set within the range of 0.1 to 999.9 sec-
onds. Set 0000 to provide normal contact outputs. The default value is 0000. The one-shot output is configurable also for
the P status.
NOTE
• The one-shot output setting prevails the OFF delay time.
• The display value and alarm indicators after a one-shot output provided are the same as those at the normal contact
output. If the display is set to blink in alarm, it starts blinking when the alarm output turns ON, and stops blinking (on)
when it is OFF, which enables the one-shot output status to be easily recognized.
10.7.1 OPERATING PROCEDURE
NOTE
The following figures are display examples. The displays
depend on the settings.
1
Hold down Alarm/
↓
button for 3 seconds or more to move on
to Alarm Setting Mode.
• The alarm output pattern is indicated.
• The SD indicates ‘ALM PTN’.
NOTE
With the bank switching set to “enabled via the front button control”, the bank No. is indicated (‘ALM BNK’ on the SD).
2
Press Alarm/
↓
or Init/
↑
button to go to the LL (L, H, HH or P)
one-shot output setting.
• The LL (L, H, HH or P) one-shot output is indicated.
• The SD indicates ‘SHOT LL’ (‘SHOT L’, ‘SHOT H’, ‘SHOT HH’ or
‘SHOT P’).
• ‘LL’ (‘L’, ‘H’, ‘HH’ or ‘P’) indicator starts blinking.
1,2,
4
2,4
3
3
Blinking
Blinking