47DM OPERATING MANUAL EM-9510-B Rev.6
4. OPERATION
Make sure that 0.000 – 100.000% is correctly indicated according to the input 2 – 8 kΩ provided with the total resistance 10
kΩ. The operation without using external control signals including the event trigger input is described here.
IMPORTANT
Before operating, make sure that the wiring is correct, the input and the power supply are within the specification range.
1
Apply 2 kΩ input (0%) and make sure that 0.000% is indicated.
NOTE
■
WHEN THE FOLLOWING IS INDICATED…
• When ‘S.ERR’ is indicated, the input is not applied correctly. Check the input
wiring, equipment and signal. When the SD indicates ‘UNDER’, the input signal
is under the specification voltage/current. And when the SD indicates ‘OVER’, the
input is over the specification voltage/current.
• When the indication is shifted with ‘FZ’ and/or ‘TZ’ indicators on, the Forced Zero
or Tare Adjustment is being executed. Cancel the Forced Zero and Tare Adjust-
ment. (Refer to 25. FORCING THE PRESENT DISPLAY VALUE TO ZERO.)
■
WHEN THE INDICATION DOES NOT CHANGE…
• MAX or MIN value is indicated with ‘Max’ or ‘Min’ indicator on. Cancel the MAX/
MIN Value Display mode. (Refer to 26. RETAINING MAX AND MIN VALUES.)
■
ALARM INDICATORS
• The status of the alarm indicators depends on the alarm setpoints. The above display examples show ‘P’ indicator on.
■
DISPLAY COLOR
• The main display color depends on the settings of the display color and setpoints.
2
Apply 5 kΩ input (50%) and make sure that 50.000% is indi-
cated.
3
Apply 8 kΩ input (100%) and make sure that 100.000% is indi-
cated.
*
1 Display depends on the settings and input.