41
47DM OPERATING MANUAL EM-9510-B Rev.6
2.1.3 BASIC SETTING PROCEDURE
The following shows the procedure to set the input to 2 – 8 kΩ with the total resistance 10 kΩ and the display to 0.000 –
100.000% as an example. Set values meeting signals of the equipment to use. Refer to 3. SETTING SCALING VALUES
for details of setting.
■
PARAMETER LIST FOR BASIC SETTING
Parameters used in the basic setting are as shown in the following table.
PARAMETER
SETTING VALUE
SUB DISPLAY
FUNCTION INDICATOR
SETTING
Input scaling value Zero
ZERO
ZERO
Zro, Tch
0% input: 2 kΩ
*
1
Display scaling value Zero
000000
*
2
DISP-Z
Zro
0% display: 0.000%
Input scaling value Span
SPAN
SPAN
Spn, Tch
100% input: 8 kΩ
*
1
Display scaling value Span
100000
*
2
DISP-S
Spn
100% display: 100.000%
Decimal point position
00.000
D-POINT
----
3 decimal places (10
-3
)
*
1 Index for description. Actual inputs are used to set.
*
2 The decimal point position depends on the decimal point position setting.
■
BASIC SETTING PROCEDURE
The basic setting procedure is as follows.
1
Confirm the wiring, and turn on the power.
• Warm up the unit for 10 minutes or more.
2
Move on to Scaling Setting Mode and set the input scaling value Zero (measurement stopped).
• Hold down Scale/
↑
button for 3 seconds or more.
• Press Up button to go to the teach calibration (Zero) setting.
• Apply 0% input and press Up button to register the value.
3
Set the display scaling value Zero.
• Press Alarm/
↓
or Scale/
↑
button to go to the next or previous parameter setting.
• Press Shift button to shift the display into the setting standby mode.
• Press Shift button to go to the next digit and Up button to change the blinking value.
4
Set the input scaling value Span.
• Press Alarm/
↓
or Scale/
↑
button to apply the new setting and go to the next or previous parameter setting.
• Press Up button to go to the teach calibration (Span) setting.
• Apply 100% input and press Up button to register the value.
5
Set the display scaling value Span.
• Press Alarm/
↓
or Scale/
↑
button to go to the next or previous parameter setting.
• Press Shift button to shift the display into the setting standby mode.
• Press Shift button to go to the next digit and Up button to change the blinking value.
6
Set decimal point position.
• Press Alarm/
↓
or Scale/
↑
button to apply the new setting and go to the next or previous parameter setting.
• Press Shift button to shift the display into the setting standby mode and Up button to select the decimal point posi-
tion.
7
Return to Measuring Mode (measurement started).
• Hold down Alarm/
↓
or Scale/
↑
button for 1 second or more to apply the new setting and return to Measuring Mode.