138
47DM OPERATING MANUAL EM-9510-B Rev.6
14. GOING BACK AUTOMATICALLY TO MEASURING MODE
The display goes back automatically to Measuring Mode if the front buttons are left untouched for the specified time period
while it is in one of the setting modes. This time period is called automatic return time and can be set within the range of 1
to 99 seconds (Table 1). With the value set to ‘00’, the display must always be exited manually from the setting mode. The
display does not go back automatically to Measuring Mode depending on the modes (Table 2).
■
TABLE 1: AUTOMATIC RETURN TIME
MAIN DISPLAY
FUNCTION
DEFAULT VALUE
Automatic return disabled
to
1 to 99 seconds
■
TABLE 2: AUTOMATIC RETURN IN EACH MODE
MODE
OPERATION
SETTING TIME OUT
Measuring Mode
Confirming and configuring alarm setpoint
Depending on setting
*
1
Displaying MAX or MIN value
Disabled
Executing Forced Zero
Disabled
Scaling Setting Mode
Enabled
Alarm Setting Mode
Enabled
Advanced Setting Mode
Enabled
Modbus Setting Mode
Enabled
Infrared Communication Mode
Disabled
Lockout Setting Mode
Enabled
Loop Test Output Mode
Disabled
*
1 Refer to 24.2 MANUAL SUB DISPLAY RESET for details.
NOTE
With the I/O option code ‘6’ or ‘A’, the event trigger mode is indicated (‘EVENT’ on the SD).