47DAC OPERATING MANUAL EM-9518-B Rev.4
11.5 ALARM TRIP ACTION AT OVER-RANGE
The alarm trip action while ‘S.ERR’ is indicated can be set with the scaling error parameter. When it is set to “alarm trip ac-
tion valid at over-range” (‘ON’), a high or low alarm output is provided depending on the ‘S.ERR’ direction. When set to “no
alarm trip action at over-range” (‘OFF’), all alarm outputs including P output and alarm indicators including ‘P’ indicator are
forcibly turned off regardless of the ‘S.ERR’ direction.
The default setting is “alarm trip action valid at over-range”.
11.5.1 OPERATING PROCEDURE
NOTE
The following figures are display examples. The displays
depend on the specifications and settings.
1
Hold down Alarm/
↓
and Scale/
↑
buttons at once for 3 seconds
or more to move on to Advanced Setting Mode.
• The averaging type is indicated.
• The SD indicates ‘AVE-TP’.
NOTE
With the I/O option code ‘6’ or ‘A’, the event trigger mode is indicated (‘EVENT’ on the SD).
2
Press Alarm/
↓
or Scale/
↑
button to go to the scaling error set-
ting.
• The scaling error is indicated.
• The SD indicates ‘SE-ALM’.
3
Press Shift and Up buttons to select the scaling error.
• Select ‘ON’ or ‘OFF’.
1,2,
4,5
1,2,
4,5
3
3
Blinking