47D Series Modbus Reference Guide EM-9501-C Rev.4
3.10 DISPLAY SETTING
ADDR. WORD CONTENTS
UNIT
6001
1
Display color
0 : Green (normal) to Red (alarm) (*)
1 : Green
2 : Red (normal) to Green (alarm)
3 : Red
6002
1
Decimal fractions for temperature input
T R
0 : No fractions
1 : 1 decimal place (*)
2 : 2 decimal places
R
(°C only)
6003
1
Round off low-digit reading
0 : 1 (*)
1 : 2
2 : 5
3 : 10
6004
1
Display refreshing rate
seconds/10
0 : Fastest possible (50 msec) (*)
1 ... 999 : Seconds
6005
1
Display reading type
0 : Measured value (*)
1 : Maximum value
2 : Minimun value
6006
1
Backlight brightness
1 (dark) ... 3 (bright)
Factory setting : 2
6007
1
LCD Contrast
1 (low) ... 10 (high)
Factory setting : 5
3.11 MODBUS SETTING
Modbus setting is enabled only after the device has been reset or the power supply has been turned off and on.
ADDR. WORD CONTENTS
7001
1
Device address
1 ... 247
Factory setting : 1
7002
1
Baud rate
0 : 1200 bps
1 : 2400 bps
2 : 4800 bps
3 : 9600 bps
4 : 19200 bps
5 : 38400 bps (*)
7003
1
Parity bit
0 : None
1 : Odd (*)
2 : Even
7004
1
Stop bit
0 : 1 bit (*)
1 : 2 bits
7005
1
T1.5 timer
1 ... 60 (character length x10)
Factory setting : 15
7006
1
T3.5 timer
1 ... 60 (character length x10)
Factory setting : 35
7007
1
Long register
0 : Normal, Low-digit word at the lower address (*)
1 : Swap, High-digit word at the lower address