manualshive.com logo in svg
background image

11

47D Series Modbus Reference Guide  EM-9501-C Rev.4

3.3  DEVICE CONTROL

 ADDR.  WORD  CONTENTS
  801 

Bank No.

 

 

 

Different sets of alarm setpoints and properties (Banks) can be selected when Master writes 1 ... 8.

 

 

 

In order to activate this setting, Bank Switching via communication must be enabled at Register 4009.

 

 

 

This register is reset to ‘1’ at the device startup.

  802 

Reset MIN / MAX values

 

 

 

MIN / MAX reading currently on the display is reset when ‘1’ is set.

 

 

 

The register value is automatically reset again to ‘0’ when the MAX / MIN value resetting action is complete.

 

 

 

If another value is set before ‘0,’ the resetting result becomes undefined.

 

3.4  LOCKOUT SETTING

 ADDR.  WORD  CONTENTS
  901 

Modbus register access control

 

 

 

0 : Read only (*)

 

 

 

1 : Write enabled

 

 

 

This register is reset to ‘0’ at the device startup.  Write ‘1’ before starting writing other registers.

 

 

 

Once ‘1’ is set, alarm and analog outputs are held at the last value and status before it has been turned ‘1.’

 

 

 

With ‘0,’ these outputs respond to the input signal.

  902 

Alarm setting lockout

 

 

 

0 : Completely unlock alarm settings

 

 

 

1 : Partially unlock alarm settings (Refer to the 47Dx operating manual for detailed information.) (*)

 

 

 

2 : Lock alarm settings

  903 

Scaling setting lockout

 

 

 

0 : Unlock scaling settings (*)

 

 

 

1 : Lock alarm settings

  904 

Advanced setting lockout

 

 

 

0 : Completely unlock advanced settings

 

 

 

1 : Partially advanced alarm settings (Refer to the 47Dx operating manual for detailed information.) (*)

 

 

 

2 : Lock advanced settings

  905 

Modbus setting lockout

 

 

 

0 : Lock Modbus settings

 

 

 

1 : Unlock Modbus settings (*)

  906 

MAX/MIN display control lockout

 

 

 

0 : Unlock MAX/MIN Display control (*)

 

 

 

1 : Lock MAX/MIN Display reset

 

 

 

2 : Lock MAX/MIN Display control

  907 

Forced zero control lockout  

V M AC

 

 

 

0 : Unlock Forced Zero and Tare Adjustment control (*)

 

 

 

1 : Unlock Forzed Zero control / Lock Tare Adjustment control

 

 

 

2 : Lock Forced Zero and Tare Adjustment control

  908 

Loop test output lockout

 

 

 

0 : Unlock Loop Test Output mode (*)

 

 

 

1 : Lock Loop Test Output Mode

(*): Factory setting

Содержание 47D Series

Страница 1: ...BUS REGISTERS 9 3 1 DEVICE INFORMATION 9 3 2 I O DATA 10 3 3 DEVICE CONTROL 11 3 4 LOCKOUT SETTING 11 3 5 INPUT SETTING 12 3 5 1 COMMON SETTING 12 3 5 2 FORCED ZERO TARE ADJUSTMENT V M AC 12 3 5 3 DC...

Страница 2: ...ymbols are as signed to Other descriptions with no specific symbol are applied to all 47D Series models Model No Function Symbol 47DV DC voltage input VV DC current input VA DC voltage current input V...

Страница 3: ...table via the control buttons at the front of the device It is also possible to change these settings via Modbus communication COMM PROPERTY SELECTION Modbus address 1 to 247 Factory setting 1 Baud ra...

Страница 4: ...for all devices connected via the RS 232C RS 485 Converter Parity bit Identical setting for all devices connected via the RS 232C RS 485 Converter Stop bit Identical setting for all devices connected...

Страница 5: ...ng Surge Protector for RS 485 422 model MD74R or MDP 4R 1 1 Insert lightning surge protectors recommended in this example if necessary Max Min FZ TZ NG Zro Spn TG Hld Tch HH H P L LL Max Min FZ TZ NG...

Страница 6: ...function code is used to read the contents of a contiguous block of holding registers measured values and set tings in the remote device REQUEST FORMAT FIELD LENGTH RANGE 1 Device address 1 byte 1 to...

Страница 7: ...123 5 Byte count 1 byte N x 2 N Number of registers 6 Register value N x 2 bytes 7 CRC 2 bytes RESPONSE FORMAT FIELD LENGTH RANGE 1 Device address 1 byte 1 to 247 2 Function code 1 byte 16 3 Starting...

Страница 8: ...CarryBit As Boolean CRC16 HFFFF For I 0 To Size 1 CRC16 CRC16 And HFF00 Or CRC16 And 255 Xor Message I For N 1 To 8 CarryBit CRC16 And 1 CRC16 CRC16 And HFFFE 2 And H7FFF If CarryBit Then CRC16 HA001...

Страница 9: ...e 0 2nd character 1st character 1 4th character 3rd character 2 6th character 5th character 3 8th character 7th character 4 10th character 9th character 5 12th character 11th character 6 14th characte...

Страница 10: ...Under scale Burnout Burnout Loop Test Loop Test mode Analog Analog output provided 3 2 Measured value 1 2 5 2 Measured value MAX 1 2 7 2 Measured value MIN 1 2 9 2 Reserved 11 2 Reserved 13 2 Reserve...

Страница 11: ...d at the last value and status before it has been turned 1 With 0 these outputs respond to the input signal 902 1 Alarm setting lockout 0 Completely unlock alarm settings 1 Partially unlock alarm sett...

Страница 12: ...s 1003 1 High pass filter 0 High pass filter OFF 1 High pass filter ON 1011 1 Low end cutout 0 Low end cutout OFF 1 Low end cutout ON 2 Low end cutout by absolute value 1012 1 Low end cutout value 0 9...

Страница 13: ...e Span Refer to Input scaling value Zero for selectable ranges Factory setting VV 50000 VA 20000 1057 2 Display scaling value Zero 20000 100000 Factory setting VV 10000 VA 04000 1059 2 Display scaling...

Страница 14: ...setting 0 F 100 5 Input compensation is not executed when the A and B values are equal 3 5 6 THERMOCOUPLE INPUT T ADDR WORD CONTENTS UNIT 1051 1 Input type 0 PR 1 K CA 1 2 K CA 2 3 E CRC 4 J IC 1 5 J...

Страница 15: ...20000 V 100 ACA 0 to 0 2mA 000000 to 002000 mA 1000 0 to 2mA 000000 to 002000 mA 1000 0 to 20mA 000000 to 020000 mA 1000 0 to 200mA 000000 to 020000 mA 100 Factory setting 000000 000000 1055 2 Input s...

Страница 16: ...UT SETTING ADDR WORD CONTENTS UNIT 3001 1 Analog output type 0 0 to 5V 1 5 to 5V 2 10 to 10V 3 0 to 20mA 4 4 to 20mA 3002 1 Analog output function mode 0 Proportional to the display value 1 Proportion...

Страница 17: ...t latched Measuring continued 2 Output and measuring latched 4006 1 Standby sequence 0 Output standing by until the input signal comes into P zone after the power is turned on 1 Output is immediately...

Страница 18: ...1 Enable 4109 2 Bank 1 H setpoint 20000 100000 V M AC V M AC Decimal point position setting 99999 999999 T R T R C 100 or F 100 Factory setting VV 38000 VA 15200 T 7000 R 7000 M 4000 AC 14000 14000 4...

Страница 19: ...H alarm trip action Identical to LL setting 4201 4206 4226 4231 6 HH alarm trip action Identical to LL setting 4201 4206 4236 4243 1 P ON delay time seconds 10 0 999 Factory setting 0 4244 1 P OFF del...

Страница 20: ...value 6006 1 Backlight brightness 1 dark 3 bright Factory setting 2 6007 1 LCD Contrast 1 low 10 high Factory setting 5 3 11 MODBUS SETTING Modbus setting is enabled only after the device has been res...

Страница 21: ...low M System will at its sole option and expense either 1 repair the defective product 2 replace the defective product or 3 refund the purchase price for the defective product paid by the purchaser Ex...

Отзывы: