48
47DR OPERATING MANUAL EM-9509-B Rev.7
4. SETTING TEMPERATURE UNIT
The temperature indication in °C (‘C’) or °F (‘F’) can be selected. The default value is °C.
IMPORTANT
“2 decimal places” setting is automatically reset to “1 decimal place” when the temperature unit is switched from °C to °F.
4.1 OPERATING PROCEDURE
NOTE
• Procedures to change ‘C’ to ‘F’ are described here.
• To change ‘F’ to ‘C’, the procedures are same. Select
‘C’ in Step 5.
1
Confirm the wiring, and turn on the power.
• All the indications turn on for approximately 3 seconds and then
the display moves on to Measuring Mode.
NOTE
• Indication ‘S.ERR’ may blink, which shows the input out of the meas-
uring range and does not show the unit failure.
• Indication ‘B.ERR’ may blink, which shows the input open or out of
the range and does not show the unit failure.
• The SD indicates the bank No. with the bank switching set to “ena-
bled”.
2
Hold down Init/
↑
button for 3 seconds or more to move on to
Initial Setting Mode.
• The input type is indicated.
• The SD indicates ‘RTTYPE’.
NOTE
Some alarm indicators turn on with the parameter display. The alarm indication is due to the last status before mode
transition held but does not show the unit failure.
3,6
2,3,
6
4,5
5
■
Immediately after power on (all indicators on)
■
Measuring Mode
*
1 Display depends on the settings and input.