Installation and Operating Instruction for
B.E.G.
-
Occupancy detectors
PD9-Master-1C/-Slave-SDB-IP65(-GH)-FC
3. Settings carried out
using remote control
(optional)
Remote control
LUXOMAT
®
IR-PD9
Check Battery:
Open battery compartment
by pressing the plastic springs
together and removing the
battery-holder.
1. Mounting preparations
Work on the 230 V mains supply
may only be carried out by qualified
professionals or by instructed persons
under the direction and supervision of
qualified skilled electrical personnel
in accordance with electrotechnical
regulations.
Disconnect supply before installing!
When in Master/Slave mode of
operation, the Master-appliance
must always be installed at the
location where there is least
daylight.
2a. Installation
4. Option:
Wall bracket for remote control
IR-PD9
The
LUXOMAT
®
PD9-M-1C-
IP65(-GH) enters an initial
60-second self-test cycle,
when the supply is first
connected. The occupancy
detector is ready for operation.
2c. Self test cycle
IR-PD9
IR-PD-Mini
B.E.G.
LUXOMAT
®
PD9-M-1C/S-SDB-IP65(-GH)
The detector has
been designed and
developed specifically
for installation in
suspended ceilings.
A circular opening of
diameter min. 32 mm
must be produced in
the ceiling.
Having connected the cables in accordance with
the regulations, connect the power supply via the
RJ11 plug. Therefore, open the power supply with
the help of the screws and close it afterwards. After
that, put the power supply through the opening in
the ceiling and mount the sensor onto the ceiling
according to figure.
2b. Connecting
terminals
8. Range of Coverage
In case the sensing area of the
LUXOMAT
®
PD9-M-1C-IP65(-GH) is too
large or areas are being covered that
should not be monitored, the range
can be reduced or limited through use
of the enclosed masking clips.
7. Exclude sources of
interference
1
Walking across
2
Walking towards
3
Seated
quer zum Melder gehen
frontal zum Melder gehen
Unterkriechschutz
9. Dimensions
GB
5. Settings by remote control
Unlocking device - Activation
of the programming mode
Locking device - Exit programming
mode
Luminance set point for channel 1
20 - 1000 Lux
Automatic reading in the current light
value as new luminance set point
Increase the current light level by
20 resp. 50 Lux
Light ON/OFF
Follow-up time (relay and channel 1)
15 sec. - 30 min.
Change between fully automatic
and semi automatic mode (HA)
Daytime operation, detector only
activated by motion
Permanent protection against
sabotage
red LED flashes
Resetting when
open:
Deletes all values
set with the
remote control,
light OFF.
or
1000
20
to
+
to
or
or
6. Key functions in closed state
15
sec
30
min
HA
ON
HA
OFF
22 - 30 mm
PD9-SDB-
MASTER-
SENSORHEAD
PD9-SDB-
SLAVE-
SENSORHEAD
N
N
L
L
TEST
1
2
4
mins
30
25
20
15
12
10
8
6
100
Lux
1500
1000
600
400
200
min. 32 mm
154 mm
25 mm
38 mm
45
25
12
16
45
24
25
16
PD9-SDB-
MASTER-
SENSORHEAD
PD9-SDB-
SLAVE-
SENSORHEAD
N
N
L
L
TEST
1
2
4
mins
30
25
20
15
12
10
8
6
100
Lux
1500
1000
600
400
200
10 m
6 m
4 m
10 m
360°
2.50 m
RJ
2
3
1
6.00 m
10.00 m
RJ
360°
6.00 m
6.00 m
3.50 m
3.50 m
PD9-M-1C-SDB-IP65
PD9-M-1C-SDB-IP65-GH
PD9-M-1C-SDB-IP65
PD9-M-1C-SDB-IP65-GH
Permanent protection against sabotage
This function blocks the unit permanently (green LED is
illuminated). This operating mode can only be activated
during the period of 5 seconds after pressing the “lock“
button. This status will only permit actuating the function
“Light on/Light off”.
The procedure for leaving this mode is as follows:
1. Switch off the current
2. Apply current for 31 – 59 seconds
3. Switch of the current again
4. Apply current
5. Open detector
Light on/off when closed
=> (see page 2, point 11)
The light will remain switched on/off for as long as
movements are detected in the areas of coverage.
Once the last movement has been detected, the light
will remain on for the duration of the follow-up time as
per setting.
The appliance will then return independently to the
mode selected (Fully or Semi-automatic).
Activation/Deactivation of the test function
Switches channel off and is immediately active again,
exits all timers, interruption of light measurement
Confirmation
Changes to „open“ state
t < 5 sec.
max
50
Lux
1500
Lux
ON
OFF
t < 5 sec.