LION microPLC
▪
Initial Operation – Hardware
32
8.5
CAN Port - X3
1. Switch off the power.
2. Connect the LION microPLC with
the devices over a suitable bus
cable.
Fig. 10: CAN Port (female), Sub-D, 9 pole, X3
Pin
Signal
Description
Connector
Housing
PE
Protective
Earth
1
PE
Not connected
2
CANL
CAN-Signal
low
3
DGND
CAN-Signal
ground
4
NC
Not connected
5
NC
Not connected
6
NC
Not connected
7
CANH
CAN-Signal
high
8
NC
Not connected
9
NC
Not connected
&$1/
&$16LJQDOORZ
'*1'
&$16LJQDOJURXQG
&$1+
&$16LJQDOKLJK
Depending on the structure of your CAN network, it must be provided with a
120Ω resistor at the beginning and end between the CAN high and the CAN low
line.
3. The switch for the CAN-Termination
resistor (8) is located to the right of
the CAN port (9).
If the switch is on the left (factory
setting), no CAN bus termination is
set.
If the switch is on the right, a CAN
bus termination resistor of 120
Ω is
set.
Fig. 11: CAN Port and CAN-Termination switch