LION Bus Coupler
▪
Error Handling
71
12.1
Error Codes
For different errors the LION webserver will display error codes which are shown
in the table below.
If the module is defect and an error code which is not described will be
displayed. Please contact the Lütze repairing service.
Error Code
Description
0x00FF0315
TDB configuration does not match the I/O station topology.
0x00FF0303
0x30300003
No or more than 32 I/O modules on the L-Bus
2
.
0x30300004
L-Bus
2
bus termination connector is missing or defect.
0x70000003
Disturbance on the L-Bus
2
:
No communication with the I/O modules.
0x10010002
0x10020002
Ambient temperature too high.
0x1001000E
0x1002000E
Ambient temperature too low.
0x00FF0301
0x00FF0302
0x00FF0308
0x00FF031E
Disturbance on the L-Bus
2
:
Start of communication is not possible.
0x00FF030B
0x00FF030E
0x00FF0319
Error during reading the TDB configuration.
0x00FF030F
Error during checking the TDB configuration.
0x00FF030A
0x00FF030C
0x00FF0314
Error during saving the TDB configuration.
0x00FF0306
0x00FF0318
Error during the configuration of an I/O module.
0x30300002
Defect of an addressing connection in an I/O module.
0x00FF031B
Safe Telegram defined on a SIL0 bus coupler.
Содержание 803012
Страница 1: ...Operating Instructions LION Bus Coupler Ethernet SIL0 LION BC ETH LUE 803012 Version 01 03 19 2019 ...
Страница 63: ...LION Bus Coupler Operation 64 Module not recognized Unexpected module ...
Страница 64: ...LION Bus Coupler Operation 65 Wrong safety checksum ...
Страница 75: ... by Lütze Transportation GmbH Weinstadt Germany Technical changes reserved ...