background image

Lutron

®

 

|

 QS Link Power Supply  

(QSPS-P1-1-50 / QSPS-P2-1-50 / QSPS-P3-1-50, 100-240 V~  50/60 Hz   
1 A Input Current)

 

Installation Instructions

Tools Required:

 Wire cutter/stripper, small flat-head screwdriver

Optional: Power drill, mounting screws
____________________________________________________________________

1

    

Important Notes:

 

Adherence to these specifications is  

necessary to ensure a safe and successful installation.

  1.   All wiring must be in accordance with national and local  

electrical codes.

  2.  Power supply should be installed by a qualified electrician.
  3.   Ambient operating temperature: 32 °F to 104 °F (0 °C to 40 °C),  

0 to 90% humidity, non-condensing.   

  4.  This product is intended for 

indoor use only

.

  5.   In Canada, separate over current protection is required, to be in  

accordance with Canadian Electrical Code, Part 1.

____________________________________________________________________

2  Installation

  1.   The power supply may be surface mounted by using the mounting tabs  

if desired. 

     -  

Unplug line voltage cable of the power supply before wiring  
low voltage terminal blocks.

  2. 

 Parts identification

 

____________________________________________________________________

3

 

QS Link Wiring

  –   

Link Rules

 -The following link rules must be observed for  

proper operation.

     a.  Use only cable with at least one twisted/shielded pair for  

communications (MUX and MUX)

     b.  Total length of power supply link (A) wire plus device link (B) wire in 

entire system must be less than 2000 ft. (609 m)

 

____________________________________________________________________

4

 

Wiring the power supply

  1.   

Run low voltage wire into the power supply

  

a.  Run the low-voltage communication wiring from the Lutron QS shade 

or keypads to the power supply (B).

     b.  Strip insulation wire so that 0.25 in. (7 mm) of bare wire is exposed. 

Make sure to tighten the screws tightly and that no insulation is inside 
of the terminal block.

     c.  Connect each wire to appropriate terminal block. 

*Note: Terminal blocks are removable for ease of wiring.

  2.   

Connecting multiple power supplies  

-  Use the 3-pin terminal  blocks when connecting communications (A) 

between multiple power supplies.  

      

     A:   

Power Supply Link

 (3-conductor)  

Communications used to connect all  
power supplies.

     B:  

Device Link

 (4-conductor)  

Provides power and communications to devices.

  3.   

Plug in line voltage and low voltage terminal blocks  
to power supply.

____________________________________________________________________

Example:

 Powering one shade  

(max of one shade per output of a power supply)

Example:

 Powering keypads

Example:

 Connecting to a GRAFIK Eye

®

 QS

Example:

 Connecting to a GRAFIK Eye QS

Maximum devices powered  

from one QSPS-P1-1-50

Total wire length of link (B)  

based on wire gauge

Shades

Controls

#12 AWG

(4 mm

2

)

#16 AWG

(1.5 mm

2

)

#18 AWG (1 mm

2

)  

GRX-CBL- 

346S-500

1 Sivoia QS  

shade

None

250 ft.  
(75 m)

100 ft.  
(30 m)

50 ft.  

(17 m)

None

Up to 8

seeTouch

®

 QS  

keypads*

1200 ft.  
(350 m)

500 ft.  

(150 m)

300 ft.  
(75 m)

* 2 seeTouch QS keypads may be exchanged for 1 control interface (QSE-CI-NWK-E)

3-pin connector 
Communication to  
additional Power supplies 

4-pin connector
Power and Communication  
to QS shade or keypads

Line voltage input

Mounting tabs

2.77 in 
(70 mm)

4.03 in 
(102 mm)

1.2 in  
(31 mm)

MUX

   

MUX  

Com

MUX

   

MUX  

+24 VDC

Com

  

LUTRON

Close

Open

Preset

LUTRON

Close

Open

Preset

LUTRON

Close

Open

Preset

Close 

Preset 

Open 

Meeting 

Videoconf 

Afternoon 

A/V Night 

Off 

LUTRON

Close

Open

Preset

LUTRON

Close

Open

Preset

LUTRON

Close

Open

Preset

... up to 8 keypads 

on link (B)

Close 

Preset 

Open 

Meeting 

Videoconf 

Afternoon 

A/V Night 

Off 

LUTRON

Close

Open

Preset

LUTRON

Close

Open

Preset

LUTRON

Close

Open

Preset

LUTRON

Close

Open

Preset

LUTRON

Close

Open

Preset

LUTRON

Close

Open

Preset

... up to 8 keypads 

on link (B)

 Devices powered by 
GRAFIK Eye QS

 Devices powered  
by supply

 Devices powered by 
GRAFIK Eye

®

 QS

Отзывы: