When installing a PowPak
TM
CCO
Module, use the supplied mounting
screws and wire the module as shown.
Note:
PowPak
TM
CCO Module may also be
mounted on or inside a junction box.
If installing unit inside a junction box please
see Application Note #423.
For more information:
www.lutron.com/powpakcco
Install PowPak
TM
CCO Module
1
All Wireless Transmitters must be installed within
30 ft (10 m) of the PowPak
TM
CCO Module.
Lutron Electronics Co., Inc.
7200 Suter Road | Coopersburg, PA 18036-1299
Suggested Installation Location:
Install in center of room.
This ensures proper RF coverage of area.
Radio
Powr Savr
TM
Occupancy
Sensor
30 ft (10 m)
Maximum
40 ft (12 m)
30 ft (10 m)
PowPak
TM
CCO Module
Install in center of room to
maximize RF coverage.
Pico
®
Wireless
Transmitter
B
C
Associate Wireless Transmitters to PowPak
TM
CCO Module
2
Hold the CCO Toggle
button on the PowPak
TM
CCO Module for 6 seconds
to enter association mode.
Hold the indicated button on a Wireless Transmitter for
6 seconds to associate the device.
Repeat for any additional Wireless Transmitters.
Hold the CCO Toggle button on the PowPak
TM
CCO Module for 6 seconds to save association(s).
A
Test
Link
Cal.
Note:
The CCO will open and
close once after each step to
confirm successful completion.
Before beginning this step, make sure that there are no other PowPak
TM
modules being set up within the same building. It is possible that Wireless Transmitters
from other systems can be incorrectly associated to this system.
Permanently Install
Wireless Transmitters
3
Note: Please consult individual
component installation guides
for information.
Test
Link
Important Notes:
Please read before installing.
•
For installation by a qualified electrician in accordance with all local and
national electrical codes.
•
Note:
Use copper conductors only.
•
Check to see that the device type and rating is suitable for the application.
•
DO NOT
install if product has any visible damage.
•
If moisture or condensation is evident, allow the product to dry completely
before installation.
•
Operate between 32 °F (0 °C) and 131 °F (55 °C).
•
0% to 90% humidity, non-condensing.
•
For indoor use only.
Part of the Energi TriPak
TM
Family
041-305
Rev. A
08/2011
PowPak
TM
| Installation
CCO Module
Start Here
FCC Information:
This device complies with part 15 of the FCC Rules and Industry
Canada licence-exempt RSS standard(s). Operation is subject to
the following two conditions:
(1) This device may not cause interference, and
(2) this device must accept any interference, including
interference that may cause undesired operation.
Modifications not expressly approved by Lutron Electronics Co., Inc.
could void the user’s authority to operate this equipment.
NOTE:
This equipment has been tested and found to comply with the
limits for a Class B digital device, pursuant to part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against harm-
ful interference in a residential installation. This equipment generates, uses
and can radiate radio frequency energy and, if not installed and used in
accordance with the instructions, may cause harmful interference to radio
communications. However, there is no guarantee that interference will
not occur in a particular installation. If this equipment does cause harmful
interference to radio or television reception, which can be determined by
turning the equipment off and on, the user is encouraged to try to
correct the interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to
which the receiver is connected.
Limited Warranty
(Valid only in U.S.A., Canada, Puerto Rico, and the Caribbean.)
Lutron will, at its option, repair or replace any unit that is defective in
materials or manufacture within one year after purchase. For warranty
service, return unit to place of purchase or mail to Lutron at 7200
Suter Rd., Coopersburg, PA 18036-1299, postage pre-paid.
This warranty is in lieu of all other express warranties, and the implied
warranty of merchantability is limited to one year from purchase. This
warranty does not cover the cost of installation, removal or reinstallation,
or damage resulting from misuse, abuse, or damage from improper
wiring or installation. This warranty does not cover incidental or
consequential damages.
LUTRON’S LIABILITY ON ANY CLAIM FOR DAMAGES ARISING
OUT OF OR IN CONNECTION WITH THE MANUFACTURE,
SALE, INSTALLATION, DELIVERY, OR USE OF THE UNIT SHALL
NEVER EXCEED THE PURCHASE PRICE OF THE UNIT.
This warranty gives you specific legal rights, and you may have other
rights which vary from state to state. Some states do not allow the
exclusion or limitation of incidental or consequential damages, or
limitation on how long an implied warranty may last, so the above
limitations may not apply to you. NEC is a registered trademark of
National Fire Protection Association, Quincy, Massachusetts. Lutron,
the Sunburst Logo, and Pico are registered trademarks and PowPak,
Radio Powr Savr and Energi TriPak are trademarks of Lutron
Electronics Co., Inc. ©2011 Lutron Electronics Co., Inc.
Need Help? www.lutron.com or call the Lutron Technical Support Center, 24/7 at 1.800.523.9466
CCO-controlled
device does
not respond
to Wireless
Transmitter(s).
•
Ensure power to the PowPak
TM
CCO
Module is properly applied.
•
Ensure the CCO-controlled device has
been properly wired to the PowPak
TM
CCO Module.
•
Ensure Wireless Transmitter is properly
associated to PowPak
TM
CCO Module.
•
Ensure Wireless Transmitter’s battery is
installed correctly.
Wireless
Transmitter(s)
cannot be
associated to
PowPak
TM
CCO Module.
• The maximum number of Wireless
Transmitters have been associated to
the PowPak
TM
CCO Module. To remove
a previously set up Wireless Transmitter,
tap the button used for association on
the Wireless Transmitter three times, on
the third tap hold for three seconds
and then tap three more times.
Troubleshooting
www.lutron.com
RMJ-CCO1-24-B
For each system ensure you have:
At Least One PowPak
TM
CCO Module.
At least one Wireless Transmitter.
Radio Powr Savr
TM
Occupancy Sensor
(6 maximum)
Radio Powr Savr
TM
Daylight Sensor
(1 maximum)
Pico
®
Wireless
Transmitter
(9 maximum)
Test
Link
Cal.
PowPak
TM
CCO Module
+
CCO
Status
LED
CCO Toggle
Advanced
Operations
Contact
Closure
Output
(CCO)
(Class 2)
Required Components
Daylight Sensor Setup
4
Turn lights in room on using the
CCO Toggle button on the PowPak
TM
CCO Module or an associated Pico
®
.
Press & hold “Cal.” on the associated
Daylight Sensor for 6 seconds.
Exit room for 5 minutes to allow
calibration to be completed.
A
B
C
A
If it is desired to have multiple zones of
lights turn on at different daylight levels
(using multiple CCO Modules with one
Daylight Sensor) follow the Tuning
procedure described in the Daylight
Sensor’s installation instructions (041-277).
Use the CCO Toggle button in place of the
Dimmer/Switch tap button referenced in
the document.
Calibration
Tuning (Optional)
24 V
~
45 mA
24 V
-
35 mA
Reset Factory Defaults
Note:
In some instances it may be necessary to reset the
PowPak
TM
CCO Module back to factory default settings.
A
Triple-tap the Advanced Operations button, “ADV”
on the PowPak
TM
CCO Module and hold until the
LED begins to flash slowly.
Within 3 seconds of flashing, release and triple-tap
the button again and the LED will flash rapidly
indicating that the unit has been reset to
factory defaults.
B
Note:
Any associations or programming previously set
up with the unit will be lost and will need to be
re-programmed.
English
Note:
Only follow this step if using a Daylight Sensor with the CCO
Module to control a device that is switching a lighting source.
Test
Link
Cal.
Note:
When wiring
CCO output
,
use 20 to 16 AWG (0.5 to 1.5 mm
2
)
solid or stranded wire.
To CCO-controlled device.
NO
(Normally Open)
NC
(Normally Closed)
COM
(Common)
Supply Voltage
24 V
~
/ 24 V
-
Note:
CCO Module supply wires can be
connected in any polarity.
Mounting screw
(2 Supplied)
Wire nut
(2 Supplied)
NEC
®
CLASS 2
CCO Information
•
This product features a single contact closure output with both
normally open (NO) and normally closed (NC) dry contacts.
•
The CCO incorporates maintained output behavior only.
•
The CCO is rated to switch resistive
loads at voltages up to 24 V only. To
properly control inductive load types
such as relays, solenoids, or motors,
refer to Application Note #434.
Transmitting
Device
Transmitted Command
CCO Default Action
Pico
®
On
NO = Close, NC = Open
Off
NO = Open, NC = Close
Raise
No Action
Lower
No Action
Preset
NO = Close, NC = Open
Radio Powr Savr
TM
Occupancy Sensor
Occupied
NO = Close, NC = Open
Unoccupied
NO = Open, NC = Close
Radio Powr Savr
TM
Vacancy Sensor
Occupied
No Action
Unoccupied
NO = Open, NC = Close
Radio Powr Savr
TM
Daylight Sensor
Ambient light below target level
NO = Close, NC = Open
Ambient light above target level
NO = Open, NC = Close
Switching
Voltage
0-24 V
-
0-24 V
~
Resistive
Load
1.0 A
0.5 A
R