When installing a PowPak
TM
Relay
Module, use the supplied conduit nut
and wire the module as shown.
If installing unit inside a junction box please
see Application Note #423.
For more information:
www.lutron.com/powpakrelay
Install PowPak
TM
Relay Module
1
All Wireless Transmitters must be installed within
30 ft (10 m) of the PowPak
TM
Relay Module.
Lutron Electronics Co., Inc.
7200 Suter Road | Coopersburg, PA 18036-1299
Suggested Installation Location:
Install in center of room.
This ensures proper RF coverage of area.
Radio
Powr Savr
TM
Occupancy
Sensor
30 ft (10 m)
Maximum
40 ft (12 m)
30 ft (10 m)
PowPak
TM
Relay Module
Install in center of room to
maximize RF coverage.
Pico
®
Wireless
Transmitter
B
C
Associate Wireless Transmitters to PowPak
TM
Relay Module
2
Hold the Relay Toggle
button on the PowPak
TM
Relay Module for 6 seconds
to enter association mode.
Hold the indicated button on a Wireless Transmitter for
6 seconds to associate the device.
Repeat for any additional Wireless Transmitters.
Hold the Relay Toggle button on the PowPak
TM
Relay Module for 6 seconds to save association(s).
A
Test
Link
Cal.
Note:
The load will flash once
after each step to confirm
successful completion.
Before beginning this step, make sure that there are no other PowPak
TM
modules being set up within the same building. It is possible that Wireless Transmitters
from other systems can be incorrectly associated to this system.
Permanently Install
Wireless Transmitters
3
Note: Please consult individual
component installation guides
for information.
Test
Link
Shock Hazard. May result in serious injury or death.
Turn off power at circuit breaker before installing the unit.
WARNING
Important Notes:
Please read before installing.
•
For installation by a qualified electrician in accordance with all local and
national electrical codes.
•
Note:
Use copper conductors only.
•
Check to see that the device type and rating is suitable for the application.
•
DO NOT
install if product has any visible damage.
•
If moisture or condensation is evident, allow the product to dry completely
before installation.
•
Operate between 32 °F (0 °C) and 104 °F (40 °C).
•
0% to 90% humidity, non-condensing.
•
For indoor use only.
Part of the Energi TriPak
TM
Family
PowPak
TM
| Installation
Relay Module
Start Here
FCC Information:
This device complies with part 15 of the FCC Rules and Industry
Canada licence-exempt RSS standard(s). Operation is subject to
the following two conditions:
(1) This device may not cause interference, and
(2) this device must accept any interference, including
interference that may cause undesired operation.
Modifications not expressly approved by Lutron Electronics Co., Inc.
could void the user’s authority to operate this equipment.
NOTE:
This equipment has been tested and found to comply with the
limits for a Class B digital device, pursuant to part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against harmful
interference in a residential installation. This equipment generates, uses
and can radiate radio frequency energy and, if not installed and used in
accordance with the instructions, may cause harmful interference to radio
communications. However, there is no guarantee that interference will
not occur in a particular installation. If this equipment does cause harmful
interference to radio or television reception, which can be determined by
turning the equipment off and on, the user is encouraged to try to
correct the interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to
which the receiver is connected.
Limited Warranty
(Valid only in U.S.A., Canada, Puerto Rico, and the Caribbean.)
Lutron will, at its option, repair or replace any unit that is defective in
materials or manufacture within one year after purchase. For waranty
service, return unit to place of purchase or mail to Lutron at 7200 Suter
Rd., Coopersburg, PA 18036-1299, postage pre-paid.
This warranty is in lieu of all other express warranties, and the implied
warranty of merchantability is limited to one year from purchase. This
warranty does not cover the cost of installtion, removal or reinstallation,
or damage resulting from misuse, abuse, or damage from improper
wiring or installation. This warranty does not cover incidental or
consequential damages.
LUTRON’S LIABILITY ON ANY CLAIM FOR DAMAGES ARIS-
ING OUT OF OR IN CONNECTION WITH THE MANUFACTURE,
SALE, INSTALLATION, DELIVERY, OR USE OF THE UNIT SHALL
NEVER EXCEED THE PURCHASE PRICE OF THE UNIT.
This warranty gives you specific legal rights, and you may have other
rights which vary from state to state. Some states do not allow the
exclusion or limitation of incidental or consequential damages, or
limitation on how long an implied warranty may last, so the above
limitations may not apply to you. Lutron, the Sunburst Logo and Pico
are registered trademarks and PowPak, Radio Powr Savr and Energi
TriPak are trademarks of Lutron Electronics Co., Inc.
©2011 Lutron Electronics Co., Inc.
Need Help? www.lutron.com or call the Lutron Technical Support Center, 24/7 at 1.800.523.9466
Load does
not respond
to Wireless
Transmitter(s).
•
Ensure breaker to the PowPak
TM
Relay
Module is on.
•
Ensure the load has been properly wired
to the PowPak
TM
Relay Module.
•
Ensure Wireless Transmitter is properly
associated to PowPak
TM
Relay Module.
•
Ensure Wireless Transmitter’s battery is
installed correctly.
Wireless
Transmitter(s)
cannot be
associated to
PowPak
TM
Relay Module.
• The maximum number of Wireless
Transmitters have been associated
to the PowPak
TM
Relay Module. To
remove a previously set up Wireless
Transmitter, tap the button used for
association on the Wireless Transmitter
three times, on the third tap hold for
three seconds and then tap three
more times.
Troubleshooting
www.lutron.com
RMJ-5R-DV-B
RMJ-5RCCO1-DV-B
With Occupancy-Status CCO
For each system ensure you have:
At Least One PowPak
TM
Relay Module.
At least one Wireless Transmitter.
Radio Powr Savr
TM
Occupancy Sensor
(6 maximum)
Radio Powr Savr
TM
Daylight Sensor
(1 maximum)
Pico
®
Wireless
Transmitter
(9 maximum)
Test
Link
Cal.
PowPak
TM
Relay Module
+
Load
Status
LED
Relay Toggle
Advanced
Operations
Contact
Closure
Output
(CCO)
(Class 2)
Required Components
(RMJ-5RCCO1-DV-B Shown)
RMJ-5R-DV-B without
occupancy-status CCO
also available.
Daylight Sensor Setup
4
Turn lights in room on using the
Relay Toggle button on the PowPak
TM
Relay Module or an associated Pico
®
.
Press & hold “Cal.” on the associated
Daylight Sensor for 6 seconds.
Exit room for 5 minutes to allow
calibration to be completed.
A
B
C
A
If it is desired to have multiple zones of lights
turn on at different daylight levels (using multiple
Relay Modules with one Daylight Sensor) follow
the Tuning procedure described in the Daylight
Sensor’s installation instructions (041-277).
Use the Relay Toggle button in place of the
Dimmer/Switch tap button referenced in
the document.
Calibration
Tuning (Optional)
120 / 277 V
~
50 / 60 Hz 5 A
1/6 HP at 120 V
~
1/3 HP at 277 V
~
Test
Link
Cal.
English
041-345
Rev. A
08/2011
CCO Information
•
Model RMJ-5RCCO1-DV-B includes a dry contact
closure output that provides occupancy status to
3rd-party equipment such as building management
systems, HVAC, and VAV controllers.
•
CCO provides both normally open (NO) and normally
closed (NC) maintained-type outputs.
•
CCO rated to switch resistive loads at voltages up
to 24 V only. To properly control inductive load
types such as relays, solenoids, or motors, refer
to Application Note #434.
Switching
Voltage
0-24 V
-
0-24 V
~
Resistive
Load
1.0 A
0.5 A
R
Reset Factory Defaults
Note:
In some instances it may be necessary to reset the
PowPak
TM
Relay Module back to factory default settings.
A
Triple-tap the Advanced Operations button, “ADV”
on the PowPak
TM
Relay Module and hold until the
LED begins to flash slowly.
Within 3 seconds of flashing, release and triple-tap
the button again and the LED will flash rapidly
indicating that the unit has been reset to
factory defaults.
B
Note:
Any associations or programming previously set
up with the unit will be lost and will need to be
re-programmed.
120/277 V
~
50/60 Hz
Conduit Nut
White
(Neutral)
Black
(Hot)
Red
(Switched Hot)
Note:
When wiring
RMJ-5RCCO1-DV-B
to 3rd-party systems, use 20 to 16 AWG
(0.5 to 1.5 mm
2
) solid or stranded wire.
To 3rd Party Equipment
To Load
NO
(Normally Open)
NC
(Normally Closed)
COM
(Common)
CCO operation affected only by
associated occupancy or vacancy sensors.
Room Occupied:
NO = Close NC = Open
Room Unoccupied:
NO = Open NC = Close