220–240 V
~
50
/
60 Hz
Hereby, Lutron Electronics Co., Inc. declares that the radio equipment type
LMM-16R-DV-B are in compliance with Directive 2014/53/EU.
A copy of the
DoC can be obtained by writing to: Lutron Electronics Co., Inc. 7200 Suter Road,
Coopersburg, PA 18036 U.S.A.
Complies with
ImDA Standards
DA103083
Lutron Electronics Co., Inc. | 7200 Suter Road
Coopersburg, PA 18036-1299, U.S.A.
RF Module | Installation
with Softswitch
Important Notes:
•
For installation by a qualified electrician in accordance
with all local and national electrical codes.
• Note:
Use copper conductors only.
•
Check to see that the device type and rating is suitable
for the application.
• DO NOT
install if product has any visible damage.
•
If moisture or condensation is evident, allow the product
to dry completely before installation.
•
Operate between 32 °F to 131 °F (0 °C to 55 °C).
•
0% to 90% humidity, non-condensing.
•
For indoor use only.
Please read before installing
Warranty:
For warranty information, please visit
www.lutron.com/TechnicalDocumentLibrary/Warranty.pdf
www.lutron.com/TechnicalDocumentLibrary/Intl_Warranty.pdf
Lutron and Softswitch are trademarks or registered trademarks
of Lutron Electronics Co., Inc. in the US and/or other countries.
©2013-2019 Lutron Electronics Co., Inc.
Load
Status
LED
Toggle
Advanced
Operations
For System Setup Guide and tools
visit www.lutron.com
RF Module
RF Module Operation
Reset Factory Defaults
Note:
In some instances it may be necessary to
reset the RF Module back to factory default settings.
A
Triple-tap the Advanced Operations (“ADV”)
button, on the RF Module and hold until
the LED begins to flash slowly.
Within 3 seconds of flashing, release and
triple-tap the button again and the LED
will flash rapidly indicating that the unit
has been reset to factory defaults.
B
Note:
Any associations or programming previously
set up with the unit will be lost and will need to be
re-programmed.
English
Customer Assistance
|
+91.124.439.0130
Asia/Middle East
|
1.844.LUTRON1
USA/Canada
|
+1.610.282.3800
Others
| www.lutron.com/support
RF Module can be installed in a junction box or
marshalling box (optional) using the conduit nut
(provided) or with mounting screws (not provided).
Please consult local and national electric codes
for proper installation.
RF Module Placement
RF Modules must be located within 30 ft (9 m) of an
RF signal repeater. RF Modules cannot be controlled
by the system until they are programmed using the
system programming software.
Shock Hazard. May result in
serious injury or death.
Turn off power at circuit breaker
before installing the unit.
WARNING
Installation:
1
2
3
10 mm
Wiring a Lever Operated Connector (shown)
When wiring lever operated connectors (3 supplied)
please use 14 AWG to 12 AWG (2.5 mm
2
to 4.0 mm
2
)
diameter solid or stranded copper wire.
Troubleshooting
Load does
not respond
to Wireless
Transmitter(s).
• Ensure breaker to the RF Module
is on.
• Ensure the load has been
properly wired to the RF Module.
• Ensure that the RF Module has
been activated in the system.
• Ensure that the Wireless
Transmitter battery is installed
correctly.
RF Module
does not
respond to
a keypad,
wireless
controller or
sensor.
•
Improper programming.
Program from the system
programming software.
•
Out of RF Range.
Reposition to be within 30 ft (9 m)
of an RF signal repeater.
•
Already at current level.
The RF
Module has already responded to
a command, or is already at the
requested setting.
•
Wireless controller or sensor
batteries low or installed
incorrectly.
Replace or install
batteries properly.
•
RF interference.
Do not run RF Module wires
with other power wires or
communication wires (e.g.,
networking, audio, or video
signals).
To Load
Live (Black)
Neutral (White)
(White)
21 mm Knockout Opening
Conduit Nut
Switched Hot (Red)
LMM-16R-DV-B
220 – 240 V
~
50 / 60 Hz 16 A
6 A Motor
041706-04
Rev. A
09/2019