Installation Guide
EcoSystem
®
5-Series LED Driver
Driver Mounting
Remove lids before mounting. Avoid mounting driver close to heat source
such as light source.
Enclosure Mounting
Correct
Lutron Technical Support Hotline +44.(0)20.7680.4481
Lutron, EcoSystem, and
)
are registered trademarks of Lutron Electronics Co., Inc.
Power Input and Digital Link Wiring
WARNING: Shock hazard.
May result in serious injury or death.
Disconnect power before servicing or installing.
For proper wiring, follow wiring schematic on driver label. Torque range
on connector screws: 0.45 N•m to 0.50 N•m.
Load Wiring
Secure Wiring
Mains Wire Size:
Use 0.75 mm
2
– 2.50 mm
2
cable
(side view)
(top view)
Solid or stranded
copper wire
8 mm
Wire Size
Digital Link
Length (max)
2.50 mm
2
500 m
1.50 mm
2
300 m
1.00 mm
2
200 m
0.75 mm
2
150 m
Ensure outer insulation extends across both rows of strain relief teeth.
Correct
Incorrect
(insulation stripped too far)
Replace the lids to clamp the wires
in place.
Tighten the screws (0.5 N•m to
0.8 N•m) and tug gently on the wires
to ensure they are secure.
Use 0.75 mm
2
– 1.50 mm
2
cable.
+V / Red
15 m Max Cable Length
LED
light
source
www.lutron.com/europe
Lid screws
To secure mounting,
insert M3.5 screws here.
Daisy Chain Wiring
To EcoSystem
R
Digital Link
compatible devices.
Note:
For EcoSystem
R
daisy chain wiring, terminals can
accept two 0.75 – 1.50 mm
2
solid or stranded wires.
EcoSystem
R
Daisy Chain Wiring
Power Daisy Chain Wiring
To additional EcoSystem
R
LED Drivers. (Maximum units
to be daisy chained: 20)
-V / Black
Incorrect
Use 0.75 mm
2
– 1.50 mm
2
cable
Note:
When placing multiple cables into the same strain relief,
all cable outside diameters must be the same.
N
L
N/C
N/C E1 E2
Primary
Digital Bus
N/C E1 E2
Digital Bus
N/C E1 E2
Digital Bus
UNIT 1
UNIT 2
N/C
N
L
Primary
N/C
N
L
Primary
UNIT 1
UNIT 2
SELV Secondary
N/C -V N/C +V
Refer to spec submittal for 15 m cable
wire gauge requirements.
041407b
P/N 041407b 01/2014