LE200 Series
LED Emergency Bulkhead
2.5W
READ THESE INSTRUCTIONS THOROUGHLY BEFORE INSTALLATION
KEEP THESE INSTRUCTIONS FOR FUTURE REFERENCE AND LEAVE
WITH THE END USER.
IMPORTANT: It is recommended that this product must be installed by a
qualified electrician or competent person. The installation must comply with
current building and IEE wiring regulations.
Lumineux accept no responsibility for injury, damage or loss, which may arise
as a result of incorrect installation, operation or maintenance.
GENERAL:
This lighting fixture is designed for permanent connection to fixed wiring which
must have suitable circuit protection by the means of the appropriate MCB or
fuse.
The product is suitable for installation on surfaces with normal flammability e.g.
wood, plasterboard and masonry. It is not suitable for highly flammable surfac-
es such as polystyrene or textiles.
LED Chips can be susceptible to damage by vapours, gases, etc emitted by other
materials, especially rubber, which can cause a reduction in light output perfor-
mance.
Therefore DO NOT introduce any parts such as alternative grommets etc. to the
inside of this fixture, other than what has been provided. Failing to observe this
and any damage caused thereby, may invalidate the warranty.
MAINTENANCE:
To avoid personal injury or damage to equipment, disconnect the power to the
light fitting before conducting any maintenance
WARNING: No user serviceable parts inside of the fixture, risk of electric shock.
Clean the lens periodically as needed to ensure continued light output perfor-
mance. Clean only with non-abrasive cloth and mild detergent if required.
WARRANTY:
This luminaire is warranted for a period of 3 years from the date of purchase.
The backup battery pack in the emergency version is warranted for a period of
24 months. The warranty could be Invalidated should the light fitting not be
installed according to these instructions, outside the scope of the specification
or the product has been altered or tampered with in any way. Please see
website for terms and conditions.
DISPOSAL:
The light source of this unit is not replaceable; when the light source reaches its
end of life the whole luminaire shall be replaced.
Disposal of Electronic Equipment WEEE Directive 2002/96/EC This product falls
within the scope of the Waste Electrical &Electronic Equipment Directive
(WEEE), which means the product should not be disposed of as normal house-
hold waste. Please recycle where facilities exist or check with your Local Author-
ity . RoHS – All components and materials used in this product are RoHS
2002/95/EC compliant.
*
Specifications may change from time to time. The information contained in this
leaflet is for guidance only and should not be considered as always accurate and
should be treated as not representative
.
UNPACKING:
This lighting fixture has been properly packed to avoid damage during transit.
Before commencing with the installation carefully inspect the luminaire to
confirm there is no damage. DO NOT INSTALL if any damage has occurred to the
fixture or any of its components.
INSTALLATION:
WARNING: Risk of electric shock! Isolate the mains power
before proceeding.
1. Remove the two front screws and lift off diffuser.
2. Press the two tabsonthehingedgear-trayandlifttorevealthe
components underneath.
3.
Openyourselectedcableentryandfeedmainscablethrough.Usethe
required IP rated gland to ensure that IP rating is maintained
4.
Connectthecablestotheterminalblockasshowninthediagram
overleaf.
5.
ForNon-Maintainedoperation,donotconnecttotheSwitchedLive
terminal.
6.
Connect the battery.
7. Return
thegear-traybackintopositionensuringnocablesare trapped
and
the locking tabs engaged.
8.
Refit the cover.
9.
Fit the screws back into the diffuser making a water tight seal.
OPERATION MODES:
To use the luminaire in maintained mode of operation keep the connected
wire link and connect the mains supply to the PERMENANT LIVE (L) and
NEUTRAL (N) connections.
For non-maintained operation remove the wire link and connect the mains
supply to the PERMENANT LIVE (L), NEUTRAL (N) and SWICHED LIVE (LS) as
required.
SPECIFICATION:
DIMENSIONS
Series
LE200
Input Voltage
220-240 V AC 50Hz
Emergency Duration
3 Hours
Battery
3.6V Ni-cd battery
Ingress Protection
IP65
Colour Temperature
6000K
Operating Temperature
0°C to +30°C
Watts
2.5W
Darwell
Darwell
220-240V AC 50Hz
3 Hours
3.6V Ni-cd battery
IP65
6000K
0ºC to +30ºC
3W
352mm
110mm
68mm
3W
12