background image

LE200 Series
LED Emergency Bulkhead
2.5W 

READ THESE INSTRUCTIONS THOROUGHLY BEFORE INSTALLATION 

KEEP THESE INSTRUCTIONS FOR FUTURE REFERENCE AND LEAVE 

WITH THE END USER.

IMPORTANT: It is recommended that this product must be installed by a   

qualified electrician or competent person. The installation must comply with 

current building and IEE wiring regulations.

Lumineux accept no responsibility for injury, damage or loss, which may arise 

as a result of incorrect installation, operation or maintenance.

GENERAL:
This lighting fixture is designed for permanent connection to fixed wiring which 

must have suitable circuit protection by the means of the appropriate MCB or 

fuse.
The product is suitable for installation on surfaces with normal flammability e.g. 

wood, plasterboard and masonry.  It is not suitable for highly flammable surfac-

es such as polystyrene or textiles.
LED Chips can be susceptible to damage by vapours, gases, etc emitted by other 

materials, especially rubber, which can cause a reduction in light output perfor-

mance.
Therefore DO NOT introduce any parts such as alternative grommets etc. to the 

inside of this fixture, other than what has been provided. Failing to observe this 

and any damage caused thereby, may invalidate the warranty.
MAINTENANCE:
To avoid personal injury or damage to equipment, disconnect the power to the 

light fitting before conducting any maintenance
WARNING: No user serviceable parts inside of the fixture, risk of electric shock.
Clean the lens periodically as needed to ensure continued light output perfor-

mance. Clean only with non-abrasive cloth and mild detergent if required. 

WARRANTY:

This luminaire is warranted for a period of 3 years from the date of purchase. 

The backup battery pack in the emergency version is warranted for a period of 

24 months. The warranty could be Invalidated should the light fitting not be 

installed according to these instructions, outside the scope of the specification 

or the product has been altered or tampered with in any way. Please see     

website for  terms and conditions. 
DISPOSAL:

The light source of this unit is not replaceable; when the light source reaches its 

end of life the whole luminaire shall be replaced.
Disposal of Electronic Equipment WEEE Directive 2002/96/EC This product falls 

within the scope of the Waste Electrical &Electronic Equipment Directive 

(WEEE), which means the product should not be disposed of as normal house-

hold waste. Please recycle where facilities exist or check with your Local Author-

ity .  RoHS – All components and materials used in this product are RoHS 

2002/95/EC compliant. 

*

Specifications may change from time to time. The information contained in this 

leaflet is for guidance only and should not be considered as always accurate and 
should be treated as not representative

.

UNPACKING:

This lighting fixture has been properly packed to avoid damage during transit. 

Before commencing with the installation carefully inspect the luminaire to  

confirm there is no damage. DO NOT INSTALL if any damage has occurred to the 

fixture or any of its components. 

INSTALLATION:

WARNING: Risk of electric shock! Isolate the mains power 
before proceeding. 

1. Remove the two front screws and lift off diffuser.
2. Press the two tabsonthehingedgear-trayandlifttorevealthe          

components underneath.

3. 

Openyourselectedcableentryandfeedmainscablethrough.Usethe               

required IP rated gland to ensure that IP rating is maintained

4. 

Connectthecablestotheterminalblockasshowninthediagram   

overleaf.

5. 

ForNon-Maintainedoperation,donotconnecttotheSwitchedLive    

terminal.

6. 

Connect the battery.

7. Return 

thegear-traybackintopositionensuringnocablesare  trapped

and 

the locking tabs engaged.

8. 

Refit the cover.

9. 

Fit the screws back into the diffuser making a water tight seal.

OPERATION MODES:
To use the luminaire in maintained mode of operation keep the connected 
wire link and connect the mains supply to the PERMENANT LIVE (L) and   
NEUTRAL (N) connections.
For non-maintained operation remove the wire link and connect the mains 
supply to the PERMENANT LIVE (L), NEUTRAL (N) and SWICHED LIVE (LS) as 
required. 
SPECIFICATION:

DIMENSIONS

Series

LE200

Input Voltage

220-240 V AC 50Hz

Emergency Duration

3 Hours

Battery

3.6V Ni-cd battery

Ingress Protection

IP65

Colour Temperature

6000K

Operating Temperature

0°C to +30°C

Watts

2.5W

Darwell

Darwell

220-240V AC 50Hz

3 Hours

3.6V Ni-cd battery

IP65

6000K

0ºC to +30ºC

3W

352mm

110mm

68mm

3W

12