Luminell Norway AS 

Doc. Nr.: L0482 

 RLX DxZ1.21 User Manual  v.1.7 

Page 3 of 9 

 

4

 

M

ARKING

 

Identification according to IECEx Scheme: 

Identification according to 2014/34/EU (ATEX): 

 
Certificate number: IECEx CML16.0048 

 
       

II 2G Ex eb mb IIC T4,T5,T6 Gb 

       II 2D Ex tb IIIC T135,T100,T85 Db 
       Ta: -55

°C ≤ Ta ≤ 55°C

 

 
Certificate number: 

CML16ATEX3108 

 

                     Ex eb mb IIC T4,T5,T6 Gb 
                     Ex tb IIIC T135,T100,T85 Db 
                     Ta: -55

°C ≤ Ta ≤ 55°C

 

5

 

C

ERTIFICATE

 

Online link to certificate:  

www.luminell.com/downloads

 

6

 

C

ONTENT

 

Box content: 

Required tools: 

 

Fully assembled  
RLX DxZ1.21 LED floodlight                           

 

User Manual 

 

Recyclable cardboard  

 

Allan Key 5mm

 

 

Flat screwdriver (2mm slot)  

 

2x 17mm combination spanners 

 

22,24 and/or 30mm combination spanner 

 

Wire stripper 

 

Additional cable glands (optional) 

7

 

S

PECIFICATIONS

 

 

Voltage Input 

AC: 100-277 VAC 50-60Hz 

 

DC: 100-300 VDC      

Current 

240W: 1,05 A @ 230 VAC 

Power factor 

cos 

 <0.98

 

Consumption 

80, 160 or 240 W (Nominal Rating) 

Ambient Temperature 

-55

°C ≤ Ta ≤ 55°C

 

IP rating 

IP66/67 

Weight 

15,2 kg  

Cable glands 

2x M25 Cable glands 
2x M20 Blind caps 

Light beam angle, temperature class and power variation see 

“Type

 

overview”

 

7.1

 

C

ABLE GLANDS

 

Make sure to replace unused cable glands with blind caps M20 or M25. Use 

55°C to >80°C rated EX 

approved cable glands if the blind caps is exchanged. Lower ambient temperature range will be limited to 
the temperature rating of the used cable gland. Warranty will be voided if replaced cable glands / blind 
caps are not UV and weather resistant. In addition, it is the installers responsibility to ensure that the cable 
and cable glands are appropriate for each other and properly sealed. For EMC compliance to MIL-STD461F 
Navy Mobil & Army, overall screening must be terminated 360° in the cable gland. 

Содержание RLX DxZ1.21

Страница 1: ...fshore conditions Remarkable EMC EMI characteristics No maintenance no flame path Prepared for GEL filled connection box CONTENTS 1 GENERAL 2 2 SAFETY 2 3 TYPE OVERVIEW 2 4 MARKING 3 5 CERTIFICATE 3 6...

Страница 2: ...on contained in these operating instructions the data and rated operating conditions disposal of waste parts or floodlight in accordance with national regulations the ATEX or IECEx certificate the equ...

Страница 3: ...Voltage Input AC 100 277 VAC 50 60Hz DC 100 300 VDC Current 240W 1 05 A 230 VAC Power factor cos 0 98 Consumption 80 160 or 240 W Nominal Rating Ambient Temperature 55 C Ta 55 C IP rating IP66 67 Weig...

Страница 4: ...the gasket if they are mechanically pushed Upon mounting ensure all gasket areas are free from any foreign objects If the silicone grease has been wiped off then add new silicone grease Loctite OKS111...

Страница 5: ...ternal electronics only cable and a variable or fixed resistor s Resistant to electromagnetic disturbance 0 10 V External low voltage supply up to 10 VDC Very common method for DIM control The RLX DxZ...

Страница 6: ...made to be maintenance free and only occasional cleaning without solvent is recommend to ensure light output and cooling Do not paint Material combination and surface treatment has been carefully sel...

Страница 7: ...Luminell Norway AS Doc Nr L0482 RLX DxZ1 21 User Manual v 1 7 Page 7 of 9 13 APPENDIX 13 1 DIMENSIONS...

Страница 8: ...4 5 13 2 MOUNTING 13 3 ACCESSORIES See Luminell com for all available accessories 1 1002600 Connection box gel kit 2 1002322 Pole Mount bracket 30 100 3 252 Protection Guard Set 4 1002629 Retrofit br...

Страница 9: ...nell Norway AS Doc Nr L0482 RLX DxZ1 21 User Manual v 1 7 Page 9 of 9 13 4 LIGHT BEAM ILLUSTRATIONS Structured glass Clear glass Types Oval 45x15 Medium 60x40 Wide 80x60 Types Spot 15 Medium 40 Medium...

Отзывы: