26
STEP 19. Connecting Current Transformers
Prior to installation, measure the CT leads
’
routing path(s) in the electrical
panel. Local electrical codes may require securing CT wiring at regular
intervals. If the provided leads are not long enough, fashion CT wire
extensions in the field. Scan the adjacent code for information on the
proper extension procedures.
When installing CTs, c
onnect CTs labeled “Line A/B CT” to the 2
-pin connector on the corresponding LSP
lead
first
. Then clamp the CT around the corresponding feeder leg as determined in the previous
steps
. The CT marked with “A” should attach to Leg A and the CT marked with “B” should attach to Leg
B. Ensure the sticker on the CT reading “This side toward grid”
is facing toward the grid/utility meter.
WARNING: HIGH VOLTAGE. MAIN SERVICE LINES ARE ALWAYS LIVE.
AVERTISSEMENT: HAUTE TENSION. LES CONDUCTEURS DE SERVICE PRINCIPAUX SONT TOUJOURS SOUS
TENSION.
CAUTION: A CT SHOULD NEVER BE LEFT CLAMPED ON A CONDUCTOR WHEN THE CT WIRING IS
DISCONNECTED. SATURATION AND DESTRUCTION OF THE CT CORE MAY RESULT. CONNECT CT WIRING
BEFORE CLAMPING. UNCLAMP BEFORE DISCONNECTING CT WIRING.
ATTENTION: UN TRANSFORMATEUR DE COURANT NE DOIT JAMAIS ÊTRE LAISSÉ SERRÉ SUR UN
CONDUCTEUR LORSQUE LES FILS DU TRANSFORMATEUR DE COURANT SONT DÉCONNECTES. LA
SATURATION ET LA DESTRUCTION DU NOYAU PEUVENT EN RÉSULTER. CONNECTER LES CÂBLES DU
TRANSFORMATEUR DE COURANT AU LSP AVANT L'INSTALLATION. DÉSINSTALLEZ LE
TRANSFORMATEUR DE COURANT AVANT DE DÉBRANCHER SON CÂBLE.
Содержание LS-100544
Страница 1: ...WWW LUMINSMART COM LS 100544 Rev 2 Lumin Smart Panel Outdoor DOCUMENTATION AND INSTALLATION MANUAL...
Страница 2: ...U S Registered Trademark Patents pending Copyright 2022 Coulomb Inc DBA Lumin All rights reserved...
Страница 4: ...This page intentionally left blank...
Страница 42: ...38 NOTES...
Страница 43: ...Lumin Smart Panel Outdoor DOCUMENTATION AND INSTALLATION MANUAL 39 NOTES...