5.5.2
Description of the MODBUS protocol implementation.
The implemented protocol is compliant with the PI-MBUS-300 Rev G specification of
Modicon.
It is important to keep in mind when configuring the parameters that the devices using
the same bus must meet the following requirements:
•
Have a unique address, different from the addresses of other devices connected to
the network.
•
The same baud rate.
•
The same type of transmission mode (single data frame format).
The N32O meters enable programming the following parameters of the RS-485 link:
•
Meter address: 1...247.
•
Baud rate: 2400, 4800, 9600, 14400, 19200, 28800, 38400, 57600, 115200 [b/s].
•
Operation mode: RTU frame format 8n1, 8n2, 8o1, 8e1.
•
Maximum response time: 50 ms.
5.5.3 Implemented functions of MODBUS protocol
The following functions of the MODBUS protocol have been implemented in the N32O
meters:
•
03 (03h) – readout of registers group.
•
04 (04h) – readout of input registers group.
•
06 (06h) – single register writing.
•
16 (10h) – registers group writing.
Fig. 16: Connecting the RS-485 interface.