Linealux
L3
LS9031
Installation Instructions
Products and specifications are subject to change without notice.
LS9031
Network Topology
- PowerSync™ Dimmable
Control Signal
120-277V
50/60Hz
120-277V
50/60Hz
Loop to next PowerSync™
Data Injector
150m (492') max
Combined length of both trunk cables can not exceed 150m (492')
PowerSync™ Topology 1
- Single Trunk Cable
10m (33') max
PowerSync™ Topology 2
- Split Trunk Cable
Maximum Circuit Load
LS6540
PowerSync™
Data Injector
LS6540
PowerSync™
Data Injector
I
I
Up to 45 luminaires per run under the following conditions:
͠
Max total cable run length 150m (492') in up to two trunk cables
͠
For run lengths in excess of 30m (100'), the
data
wire gauge cannot exceed 14 AWG (2.5mm
2
)
͠
For run lengths up to 30m (100'), the
data
wire gauge is not governed
͠
Refer to 'Maximum Circuit Load' table for circuit limitations
͠
Always observe local electrical codes for branch circuit current limitations
Terminator
Use PowerSync™ terminator, supplied with
leader cable to terminate last luminaire
in chain.
T
Maximum Current
≤16.0A through cables and connectors
supplied by Lumascape
≤12.8A applies to connectorised
installations in North America
I
Connection Type
Circuits can be configured as either
connectorised or hardwired. For details
consult installation instructions and comply
with local electrical codes.
T
T
T
Maximum Number of Interconnected Fixtures
Luminaire
Length
LED Power
120V
240V
277V
12A
16A
12A
16A
12A
16A
1ft
5W
45
45
45
45
45
45
12W
45
45
45
45
45
45
2ft
5W
45
45
45
45
45
45
12W
40
45
45
45
45
45
3ft
5W
45
45
45
45
45
45
12W
26
35
45
45
45
45
4ft
5W
42
42
45
45
45
45
12W
20
26
40
45
45
45
Refer to PowerSync™ installation manual for maximum distance information and typology options.
All connectorised options in North America are limited to 12.8A branch circuit load.
For non-continuous runs contact factory for details.
Local wiring rules and requirements may limit circuit loadings. Refer to relevant electrical parameters to calculate.