INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

 

  WSG GRILAIR WEATHER-PROOF LOUVRES  

In principle, avoid all damage caused by external influ-
ences. Do not lift the louvres by the slats. Louvres with 
a maximum weight of 50 kg can be lifted by the 
C-profile frame. With heavy louvres use the ring bolt 
suspensions provided. Do not use individual slats under 
any circumstances as footholds during installation. 
Any damage, e.g. deformation of the slats, dents, im-
pacts, frame warpage etc. can lead to insufficient 
water drainage and undesired flow generated noise. 
Report all damage immediately to the supplier or 
manufacturer. 

PRODUCT DESIGNATION    

WSG-50…, WSG-75…, WSG-h…, WSG-SDf…, WSG-SDs… 
          

TECHNICAL SPECIFICATIONS

Max. size W x H:     

1-part max. 4000 x 8000 mm (subject to shipping)

ATEX

  

 

WSG dampers are only approved in specific designs and with 

   appropriate identification for Zones 1, 2, 21 and 22 according 
   to ATEX Directive 94/9/EC.
   If the fitter or operator changes the louvres in any way, the 
   ATEX approval becomes null and void. It is important to ensure 
   that the louvres and additional equipment are installed in 
   compliance with zoning requirements.

SHIPMENT

INSTALLATION

Damage may impair the proper functioning of the 
louvre and at best cause dangerous circumstances to 
occur. 

ATEX:

 Under no circumstances may ATEX louvres be 

fitted after a fall or impact with visible or concealed 
damage.

WSG-50 

&

 WSG-75:

 These louvres are only suitable 

for vertical applications. The louvres must be adequa-
tely sealed to fixtures and in the area of flanges. This is 
the responsibility of the planning engineer or fitter.

WSG-h 

&

 WSG-SDf 

&

 WSG-SDs:

 These WSG mo-

dels require a base frame construction which must be 
produced by the customer. With louvres which are 
larger than 4 m² or with multipart louvres, the custo-
mer must produce additional support structures in the 
area of the surrounding water duct. The planning 
engineer or fitter is responsible for sufficient support. 
The louvre is placed and fixed to the structure men-
tioned above. Make absolutely sure that all the sur-
rounding flanges are seated properly after the louvre is 
positioned. To ensure drainage of water from the lower 
slats, the louvre must be installed with a slight inclina-
tion in the direction of the slats. 

The louvre is then ready to operate after an air duct 
and water drains are connected without warpage.

ATEX:

 All relevant national and international stan-

dards and regulations for Ex zones must be observed. 
On louvres with ATEX functionality in particular, the 
louvre housing must be earthed using the earthing 
braids attached by the manufacturer. No mechanical 
changes may be made to the product. In addition do 
not attach any components (frost monitors, tempera-
ture sensors, etc.) to the louvres if they have not been 
analyzed for ignition risk by the appropriate manufac-
turers or approved for ATEX zones. 