363-205-401
Power Up:
Issue 7, March 1997
Page 1 of 6
DLP-506
Install 336A Rectifiers in J1C182BA Power Shelf
SUMMARY: Insert 336A RECTIFIER into power shelf. Measure
−
42 to
−
56 V DC at
LDU (
−
48B/GND). Unseat 336A RECTIFIER and repeat for additional 336A
RECTIFIERs. Reseat all 336A RECTIFIERs.
1.
NOTE:
Two 336A RECTIFIERs are required for one dual bank assembly and an
additional two 336A RECTIFIERs (total of four) are required for a second
dual bank assembly.
Get required number of 336A RECTIFIERs and inspect for possible physical
damage.
2.
NOTE:
All BATTERY CHARGERs must be unseated throughout this procedure.
Verify that fuse on 336A RECTIFIERs (Figure 1) is not blown.