4-8
Issue 5
May 1997
363-208-010
Parts Lists and Kits
Cross-connect Blocks
Miscellaneous Cables
Tools
*
Registered trademark of Thomas & Betts, Corp
VF
100 pair blocks (2 required per MDS Assembly)
DS1
Optional blocks to terminate 28 shielded pairs each, transmit and
receive
Fiber Optic
Block to terminate up to 8 (metallic distribution applications) or up
to 40 single-mode fibers (fiber distribution - HDOS systems)
Power
< 30 feet:
Two 10-gauge pairs
> 30 feet:
Two pairs gauged to limit D.C. drop to 1.5v maximum at
25 amps spliced down to 10 gauge before connecting to
ARM shelf Power Interface Unit.
Ground
No. 2 AWG ground wire or equivalent to meet local building standards
Fiber Optic
One pair, single-mode fiber cables per
SLC-2000 OLIU circuit pack
One single, single-mode fiber cable per HDOS OU circuit pack
Ringing
Two 20-gauge twisted triples
Basic
Hand tool kit (screwdrivers, wrenches, pliers, etc.)
Large tool kit (hammers, claw bar, level, etc.)
Floor drilling equipment (roto-hammer, masonry bits) drop-in
anchors may be furnished by supplier
Lifting equipment (hoists, dolly trucks, straps, etc.)
Special
Wire wrap tools (gun, bits for 22, 24, and 26 gauges)
Cable crimpers (battery and ground lugs)
TY-RAP* tool
Test Equipment
Digital volt/ohmmeter
Содержание SLC-2000 Access System Central Office Terminal
Страница 1: ...SLC 2000 Access System Customer Assembly Manual for RT Frames 363 208 010 Issue 5 May 1997...
Страница 4: ...This page is intentionally blank...
Страница 10: ...viii Issue 5 May 1997 Contents...
Страница 16: ...xiv Issue 5 May 1997 Tables...
Страница 24: ...1 ii Issue 5 May 1997 Contents General Information...
Страница 34: ...2 iv Issue 5 May 1997 Tables Installation Procedures 2 1 Dimensions for Figure 2 2 6...
Страница 66: ...3 viii Issue 5 May 1997 Contents Cabling Wiring and Assembly...