363-208-010
Cabling, Wiring, and Assembly
Issue 5
May 1997
3-47
DC Power Connections
Step 1:
Connect the office battery -48v and return leads as follows:
Ringing Connections
Step 1:
Connect the office ringing supplies to the PIU TS1 terminals as follows
Table 3-3. PIU/J1C182BC Ringing Supply Shelf Terminal Assignment
-48v A
terminal 1
-48v A RTN
terminal 2
-48v B
terminal 3
-48v B RTN
terminal 4
Power Interface Unit
Ringing Supply*
Designation
TS1
P116
Color**
20Hz A RTN
terminal 5
2
black
+20Hz A
terminal 6
3
white
-20Hz A
terminal 7
1
red
20Hz B RTN
terminal 8
5
black
+20Hz B
terminal 9
6
white
-20Hz B
terminal 10
4
red
* Refer to APPLICATIONS chapter for ringing supply interconnec-
tions.
** ED7C723-35, G9 cable assembly color codes for J1C182BC Ring-
ing Supply Shelf