inc. (from DSX) DS3 LOS
....................................................................................................................................................................................................................................
inc. (from DSX) DS3 LOS
At least 128 consecutive zeros are received in the DS3 signal
incoming from the DSX-3, or the energy at the DS3 input is below a
present threshold.
Alarm Data
Value/Meaning
Reported Alarm
Level(s)
Critical (CR), Major (MJ), Minor (MN), Not
Alarmed
CR is the default level.
AID (type)
DS3 Port
Date
month/day/year that condition was detected
Time
hour:minute:second that condition was detected
Probable Cause
LOS
Effect on
Service
CR, MJ, MN = SA or NSA
Not Alarmed = Standing Condition (SC)
Alarm Entity
Type
T3
Description
inc. (from DSX) DS3 LOS
Likely Cause
Hard failure of interfacing customer equipment or
facility (towards the DSX-3). The DS3 input is
disconnected at the backplane or the DSX-3;
equipment is failed or removed at DSX-3.
Visible
indication
Lighted
CR
/
MJ
or
MN/ABN
LED on SYSCTL
faceplate and a flashing
FAULT
LED on the
alarmed circuit pack.
Action
Proceed to
Alarms, conditions, and error messages
....................................................................................................................................................................................................................................
3 - 4 4
Lucent Technologies
365-372-333 R2.1
Issue 4, June 2005