Ordering Information 3 - 1
3
Ordering Information
Equipment Lists
Table 3-A shows the available equipment lists for the Lineage
®
2000 J85502B-1 rectifier. List E or F and List 1 or 2 are required
depending on output voltage and controller used with the
rectifier. The other six lists are optional.
Table 3-A: Equipment Lists for the J85502B-1 Rectifier
List Number
Input Voltage (AC)
Output Voltage
(DC)
1
208 or 240
±24
2
208 or 240
±48
E
434A voltage monitor board
without ac voltage alarm
F
434B voltage monitor board
with ac voltage alarm
Optional List
Number
Provides
10
Digital meter
20
Inrush current controlling unit
WA
External sensing, required when rectifier
is installed with a controller equipped
with battery regulation fuses
WB
External high voltage shutdown
(HVSD), required when rectifier is
installed with controller that provides
signal for external HVSD
B
Circuit breaker in positive output lead
(negative ground system)
C
Batteryless power plant