Lucent Technologies Lineage
®
2000 50A Ferroresonant Rectifier J85502B-1
2 - 10 Product Description
Issue 6 May 1999
Table 2-B: Physical and Thermal Characteristics of the J85502B-1 Rectifier
Output DC
±24V
Output DC
±48V
Dimensions (inches)
23.25 wide x 10 tall x deep
Weight (pounds)
160
180
Heat dissipation*
BTU/hr at full load
845
1025
Humidity rating
10% to 95% (non-condensing)
Operating altitude
Sea level to 10,000 feet (3048 meters)
Operating temperature
35° to 122°F
1.5° to 48.8°C
Audible noise at 5 feet
above floor and 2 feet in
front of rectifier
Less than 65 dBA
Earthquake rating
Meets Zone 4 per Bellcore
TR-EOP-000063 (Issue 3)
*Measured at 28 Vdc (24-volt rectifiers) and 54 Vdc (48 volt rectifiers).
Table 2-C: Input Specifications for the J85502B-1 Rectifier
Input AC (Volts)
Nominal Line Current (Amps)
Frequency (Hz)
Nominal
Range
±24V
±48V
208
184-220
8
15
60±3
240
212-254
7
13
Data recorded at full load, 28 Vdc for 24-volt rectifiers and 54 Vdc for 48-volt rectifiers.
Table 2-D: Output Specifications for the J85502B-1 Rectifier
Nominal
Rectifier
(amps/
volts)
Output
Range
(amperes)
Output
Range
(dc volts)
Minimum
Efficiency*
at Full Load
(percent)
Minimum
Power
Factor at
Full Load
AC Ripple **
(mV peak to
peak)
Standard
Filter
Maximum
Noise at
Battery**
(dBrnc)
Standard
Filter
50/24
0 - 50
21.5 - 28.0
85
.97
100
32
50/48
0 - 50
43.0 - 56.0
90
.95
100
32
*Efficiency measured at nominal line, 28 Vdc or 54 Vdc.
**Measured 200 amp/hr battery (4 times rectifier capacity) with a 2-volt lead drop
for standard and 0.5-volt drop for optional filter.