Legend:
*1
Shielded MDI/MDO cable
→
all pins should be connected to
the MDIO terminal rail (one-by-one). The cable should be
shortened to the appropriate length.
*2
Preferred earth connection point for the braid of the MDI/MDO
cable.
*3
One of the Ualm (-48 V) connection points (5, 6, 7 or 8)
should be connected to pin 5 of the MDIO terminal rail.
*4
Cable to external equipment (e.g. temperature sensor). The
same shielded cable must be used as is used between the
subrack (CI-CTL) and the MDIO terminal rail.
Routing without MDIO terminal rail
An external equipment (e.g. temperature sensor) can also be connected directly to the
MDI/MDO interface of the subrack. In that case the common pin (= pin 5) has to be
connected to a voltage in the range of -40 V ... -72 V on the customer side.
Figure 4-36 Routing via the MDIO terminal rail
System cabling and final assembly
Miscellaneous Discrete Inputs/Outputs (MDIs/MDOs)
.................................................................................................................................................................................................................................
365-374-187
Issue 1, December 2005
Lucent Technologies - Proprietary
See notice on first page
4-57