Power wiring (External battery - PDP)
.................................................................................................................................................................................................................................
Before you begin
Before connecting any power cables be sure that all circuit breakers that are located in
the external Battery Distribution and Fuse Bay (BDFB) and on the rear side of the
subracks (on the Power Interfaces) are in the
OFF
position!
Cable data
Depending on the length the following power input cables can be used:
•
Power input cable 25 m [82.021 ft] — CC848852745
•
Power input cable 16 m [52.493 ft] — CC848852653
•
Power input cable 5 m [16.404 ft] — CC848852752.
NOTE:
Two power input cables are needed for each subrack.
Connection points
The following figure shows the connection points at the PDP.
Figure 4-2 PDP connection (power input cables)
+DC (rtn)
(A+B)
1
2
-DC
(A+B)
*
Power input cables, upper subrack
Power input cables, lower subrack
System cabling and final assembly
.................................................................................................................................................................................................................................
365-374-187
Issue 1, December 2005
Lucent Technologies - Proprietary
See notice on first page
4-7