Lucent Technologies Lineage
®
2000 ECS-12 Controller J85501D-2
4 - 4 Installation and Setup
Issue 3 August 1998
Frame Mounting
The controller should arrive configured for 23-inch frame
mounting. For 26-inch mounting in plants such as J85500A, B,
or C, the two mounting brackets may be removed and rotated as
indicated on the controller assembly drawing, J85501D-2.
1. If the ribbon cables for the LVD/Fuse Board interface and
rectifier interfaces are not already plugged into the
controller, attach them to the rectifier multiplexing circuit
pack (BCC1) and dress them as shown on the assembly
drawing. Use wire ties as needed to secure the ribbon
cables.
2. Using the mounting screws, attach the controller to the
framework in the desired location.
3. Dress the ribbon cables from the controller to the
LVD/Fuse Board and rectifier interfaces as indicated on
the plant assembly drawing or battery plant product
manual.
4. Proceed with “Hardware Setup.”
Hardware Setup
Refer to Figures 4-1 and 4-2 for backplane and CP1 set-up,
respectively. The LVD/Fuse Board is shown in Figure 4-4.
CAUTION
Circuit packs can be damaged by static electricity.
Operators should always wear a grounded wrist strap
plugged into the controller front panel when touching or
handling circuit packs.
There are jumper straps located on the backplane, the 113B
Control Unit (CP1), and the LVD/Fuse Board (CP5) that must be
set properly before powering the controller. These jumpers are
set at the factory with proper settings for the plant in which the
controller is shipped. In shipped-loose controllers, the jumpers
are factory configured for 48-volt operation.
CAUTION
Applying power to the controller when jumper straps are
improperly arranged may damage the controller circuit
packs.