Lucent Technologies Lineage
®
2000 ECS Battery Plant H569-403
Issue 4 February 1997
Maintenance 5 - 7
5. Reconnect quick connect leads to new contactor and then
mount new contactor using hardware from Step 4.
6. Plug P501 into J501 on LVD/Fuse board (CP5) and verify
that contactor closes.
7. Replace rectifier and turn on.
8. Close LVD/fuse panel door and verify that LVD FAIL and
LVD OPEN lights are not lit.
LVD/Fuse Board
(CP5)
Replacement
The following equipment is required:
•
Standard screwdriver
Procedure: (Refer to Figure 4-3 and T-83118-30 drawing)
1. Open distribution panel.
2. Unplug the following connectors from the LVD/Fuse
Board (CP5). Leave the cables dressed.
■
J502 from P502
■
J508 from P508
■
J506 from P506
■
J501 from P501
■
J504 from P504
■
Wires from TB501
3. Remove the 6 mounting screws.
4. Set jumpers J505.1 and J505.2 on replacement LVD/Fuse
Board (CP5). See H569-403 drawing for desired
disconnect voltage.
5. Mount the replacement board to the distribution panel
using the hardware from Step 3.
6. Reconnect the following connectors:
■
J502 to P502
■
J508 to 508
■
J506 to P506
■
J501 to P501
■
J504 to P504