© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED
WMSOU-xx-P0x_DBL_LST_EN_0804.PDF • PAGE 1
A
Building Safety. Building Security.
Description
The loop powered multitone sounder is fi tted into a round
plastic case. It is powered and actuated as a module via
the ADM loop with System Sensor/200 protocol.
The sounder can be activated by a Fire Detection Con-
trol Panel Series BC216 with two different tone types,
depending on the parameter setup. One of 32 different
tone type combinations can be selected with a DIL-
switch. The following tones are available, for example:
• Continuous tone 660Hz,
• Emergency signal according to DIN 33404,
• Slow whoop tone according to NEN 2575,
• Alternating tone 800/970Hz, and many more.
The sound level can be selected in 3 steps. The address
of the sounder is selected with two decadic rotary swit-
ches located at the bottom of the device.
The sounder is designed for indoor and outdoor wall
mounting. For this purpose a special base is needed.
Various base types for protection classes IP24, IP44
or IP65 are available, depending on the application. An
optional mounting plate can be supplied for surface
mounted cabling.
The sounder is available in two colours and two diffe-
rent versions: With or without integrated dual-isolator
module.
• ADM loop technology with
System Sensor/200 protocol
• Can be activated with two different
tone types, 32 tone types selectable
• Sound level selectable in three steps
– up to 100db(A)
• Low power consumption
• Versions with or without integrated
dual-isolator available
• Various base types available
Specifi cations
Operating voltage
Supply through loop voltage
Sound level
typ. 82dB(A) at 1m distance (low)
typ. 90dB(A) at 1m distance (medium)
typ. 96dB(A) at 1m distance (high)
max. 100dB(A) at 1m distance (high)
Ambient temperature
-25°C to +70°C
Dimensions ø × H
115 × 68 (mm) (incl. base LPBW)
Weight
204g