background image

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED

UVIR2-16591_DBL_LST_EN_0850.PDF • PAGE 1

A

Building Safety. Building Security.

Description

•   UV sensor combined with dual IR 

sensor, according to EN 54-10,

Class 1

•   Detection of open fl ames through 

fl ickering IR and UV radiation

•   Highest immunity to deceptive alarms
•  Selectable response delay
•   Relay contacts for alarm and fault
•  Integrated optical test function

The Flame Detector 16591 responds to the fl ickering 

infrared and ultraviolet radiation of open fl ames. There-

fore, it is extremely well suitable for the detection of 

fi res which are diffi cult to detect with common smoke 

detectors – for example, alcoholic fi res or gas fl ames.

The detector is ideal for the following applications:

  • Aircraft hangars

  • Power stations and turbine plants

  • Military bases

  • Nuclear facilities

  • Fuel depots

Thanks to the combination of two independent infrared 

sensors for different wavelengths and an UV sensor as 

well as an intelligent evaluation logic, the detector can 

distinguish particularly safely between alarm situations 

and deceptive alarms. Therefore, it is very insensitive 

to  disturbance  sources  such  as  sunlight,  fl uorescent 

lamps or electric arcs.

The detector complies with EN 54-10, Class 1, which 

means it is suitable to detect fl ames up to a distance 

of 25m.

The response delay of the detector can be selected in 

4 steps between 1 and 8s. An alarm and a fault conditi-

on is signalled via two dry relay contacts. Conventional 

technology  is  used  for  alarm  transmission  to  the  fi re 

detection control panel. The detector can be integra-

ted into an ADM loop by means of a conventional zone 

module.

A  simple  test  of  the  detector  can  be  carried  out  by 

means of the integrated optical self test function, which 

does not require additional tools. During this self test, 

built-in infrared and ultraviolet light sources simulate a 

fi re situation which activates the detector.

The detector has been designed for indoor and outdoor 

use. The optional Detector Mounting Bracket 7127 al-

lows stepless horizontal and vertical adjustment for the 

easy adaptation of the detector to the required monito-

ring area.

For use in explosion-hazardous areas, an Ex version of 

the fl ame detector is available on request.

Отзывы: