background image

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED

M510E-4-20_DBL_LST_EN_0913.PDF • PAGE 1

A

Building Safety. Building Security.

Description

•   ADM loop technology with

System Sensor/200 protocol

•   Monitored analogue input with 

sensing range 4 – 20mA

•   Connection of analogue sensors such

as gas detectors or fl ame detectors

•  Current-limited sensor circuit
•   Mounting by means of

Surface Mounting Box SMB500

The  Monitor  Module  M510E-4-20  is  designed  for  the 

connection  of  analogue  sensors  with  a  4  –  20mA 

 current interface.

With that, all sensors that are equipped with a corres-

ponding analogue output – for example, gas detectors 

or fl ame detectors – can be integrated into a fi re detec-

tion system. By means of the module, sensors in 2- or 

3-wire technology can be connected.

The sensor circuit is powered by connecting an exter-

nal power supply to the module. The integrated current 

limiter prevents overloading of the module if the power 

supply for the sensor is short-circuited. In addition, the 

current-limited  analogue  input  is  monitored  for  wire 

 breakage.

The  Monitor  Module  M510E-4-20  is  integrated  into 

an  ADM  loop  with  System  Sensor/200  protocol  and 

 occupies one address in the number range of detector 

addresses.

The  two-coloured  status  LED  is  actuated  by  the  fi re 

 detection control panel and indicates the activated con-

dition and fault condition of the sensor.

The  module  is  designed  for  mounting  in  a  Surface 

Mounting Box SMB500.

Specifi cations

Operating voltage 

Supply through loop voltage

Current consumption on the loop 

max. 700µA (normal communication)

External power supply 

12 – 28VDC

Current consumption external power supply 

typ. 10mA (24V, without sensor)

Current limiting, sensor supply (3-wire technology) 

500mA

Current limiting, analogue input 

25mA

Ambient temperature 

-10°C to +60°C (no icing)

Relative humidity 

10 – 95% (no condensation)

Dimensions L × W × H 

121 × 107 × 32 (mm)

Weight 

100g

Order number 

249112

Order name 

Monitor Module 1xAnalog In/SS M510E-4-20