Building Safety. Building Security.

Description

Specifi cations

The Safety Barrier ES58-2 for the galvanic  isolation of 

the detectors in the hazardous area serves for the de-

sign of an intrinsically safe electric circuit. The  plastic 

surface-mount housing allows to mount the safety bar-

rier near the hazardous area.

The built-in zener barrier limits the current and the vol-

tage of the detector line, as well as the electric energy 

stored  in  the  intrinsically  safe  circuit.  The  maximum 

number of detectors depends on the country-specifi c 

regulations and can be found in the Connection of De-

tectors.

Due to the galvanic isolation, the earth leakage moni-

toring can remain activated in the fi re detection control 

panel. Thus, the installation can also be monitored in 

the hazardous area.

•   Allows to create intrinsically safe 

circuits

•   Galvanic isolation of the detector line 

voltage

•   Connection of intrinsically safe 

detectors

•    Industrial plastic surface-mount case
•  ATEX certifi ed

Ignition protection 

intrinsically safe

Ex classifi cation 

EEx ia llC 

Operating voltage 

Supply through the detector line voltage

Quiescent current 

approx. 5mA

Ambient temperature  

-20°C to +60°C

Dimensions W × H × D 

120 × 160 × 90 (mm)

Colour 

light grey, similar to RAL 7035

Weight 

650g

Approval 

BASEEFA98ATEX7343

Order number 

228003

Order name 

Safety Barrier/Conv. ES58-2