2.13.13 Sounder-Strobe FLASHNI-SV with separate actuation
DIP switch 1 is used for setting the sound level: 0 = low; 1 = high.
The DIP switches 2 through 6 allow you to set the tone.
DIP switch
2
3
4
5
6
Tone 1
1
1
0
0
0
1200-500Hz DIN tone
1
1
0
0
1
500-1200Hz Slow whoop tone
1
0
0
1
0
970Hz – BS tone