background image

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED

Ex-ApoDisc_DBL_LST_EN_0804.PDF • PAGE 1

A

Building Safety. Building Security.

IS Optical Smoke Detector AOEX-55000-640

•   ADM loop technology with

Apollo/Discovery protocol

•  Optical smoke detector
•  Thermal detector
•   Safety barrier with galvanic isolation
•   Protocol interface for communication 

with the fi re detection control panel

•   ATEX certifi ed

Specifi cations

The  addressable  Intrinsically  Safe  Optical  Smoke  De-

tector AOEX-55000-640 (fi g. A) uses the scattered light 

principle and was developed for the detection of smo-

ke particles in hazardous areas. The smoke detector 

must always be connected via a safety barrier, which 

has  been  approved  for  this  detector,  and  a  protocol 

interface.  Furthermore,  the  relevant  country  specifi c 

regulations always have to be observed.

The proven ADM loop technology with Apollo/Discovery 

protocol  establishes  a  permanent  communication  be-

tween the fi re detection control panel and the detector. 

That ensures a periodical function testing of the detec-

tor. In the control panel all types of fi res are detected by 

continuously comparing fi re patterns.

Intelligent evaluation algorithms use the current condi-

tion of the sensing chamber to predict the likely time 

of the next maintenance. Thus the alarm threshold is 

automatically adjusted within the permissible range, de-

pending on the contamination. With that, the constant 

response  sensitivity  of  the  detector  is  ensured  for  a 

long time.

The two LEDs with 360° visibility indicate the activated 

condition of the detector. The detector address is se-

lected by means of a code card in the detector base. 

Therefore the detector can be changed without additi-

onal tools.

The detector is inserted into the IS Detector Base ASEX-

45681-215  (not  illustrated)  and  it  can  be  protected 

against theft.

Ignition protection 

intrinsically safe

Ex classifi cation 

EEx ia IIC T5

Operating voltage 

Supply through loop voltage

Current consumption 

typ. 340µA (quiescent)

Ambient temperature 

-20°C to +40°C (no condensation or icing)

Relative humidity 

0 – 95% (no condensation)

Dimensions ø × H 

100 × 42 (mm)

Colour 

white

Weight 

100g

fi g. A

fi g. B

fi g. C

fi g. D