109
Learning Basic Features
4.9 Reset and Restart
Reset and restart operations can be setup for inverter operation following a fault trip, based
on the terminal block operation command (if it is configured). When a fault trip occurs, the
inverter cuts off the output and the motor will free-run. Another fault trip may be triggered if
the inverter begins its operation while motor load is in a free-run state. In PRT-08, bit 1 sets
the option for all the fault trips, other than low voltage trips, and bit 2 sets the option for low
voltage trips. PRT-10 sets the delay time for restart (the time for the inverter to wait before it
restarts).
The number of auto-restarts (PRT-09) refers to the number of times the inverter will try
restarting its operation. If fault trips occur again after restart, the retry number counts down
each time the inverter restarts until the number becomes ‗0.‘ Once the inverter restarts
successfully after the initial fault trip, the inverter does not restart until the next fault trip
occurs. The number of auto-restarts set at PRT-09 that decreased after a restart reverts to
the original setting value if successful operation continues for certain period of time.
Group Code Name
LCD
Display
Parameter Setting
Setting
Range
Unit
DRV 06
Command source
Cmd
Source
1 Fx/Rx-1
0
–5
-
PRT
08
Reset restart setup
RST
Restart
00
00
–11
Bit
09
No. of auto restart
Retry
Number
6
0
–10
-
10
Auto restart delay
time
Retry
Delay
5.0
0.1
–600.0
sec
Содержание H100
Страница 14: ......
Страница 18: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Страница 27: ...Preparing the Installation 13 ...
Страница 47: ...33 Installing the Inverter ...
Страница 48: ...Installing the Inverter 34 Input and Output Control Terminal Block Wiring Diagram ...
Страница 61: ...47 Installing the Inverter ...
Страница 71: ...Learning to Perform Basic Operations 57 ...
Страница 88: ...Learning to Perform Basic Operations 74 ...
Страница 103: ...89 Learning Basic Features Code Description V1 Quantizing ...
Страница 120: ...Learning Basic Features 106 Grou p Cod e Name LCD Display Parameter Setting Setting Range Unit Prev ...
Страница 129: ...115 Learning Basic Features ...
Страница 140: ...Learning Basic Features 126 ...
Страница 148: ...Learning Basic Features 134 ...
Страница 171: ...157 Learning Advanced Features Deceleration dwell operation ...
Страница 183: ...169 Learning Advanced Features ...
Страница 184: ...Learning Advanced Features 170 PID Command Block ...
Страница 185: ...171 Learning Advanced Features PID Feedback Block ...
Страница 186: ...Learning Advanced Features 172 PID Output Block ...
Страница 187: ...173 Learning Advanced Features PID Output Mode Block ...
Страница 197: ...183 Learning Advanced Features ...
Страница 201: ...187 Learning Advanced Features Code Description 100 EPID1 Control block ...
Страница 202: ...Learning Advanced Features 188 EPID2 Control block ...
Страница 237: ...223 Learning Advanced Features Time Period Schedule AP3 38 Except3 Day 01 01 ...
Страница 244: ...Learning Advanced Features 230 ...
Страница 259: ...245 Learning Advanced Features Code Description Code Description Volt ...
Страница 362: ...Learning Protection Features 348 ...
Страница 415: ...401 RS 485 Communication Features Item Standards Parity check None ...
Страница 524: ...Table of Functions 510 ...
Страница 533: ...Table of Functions 519 ...
Страница 547: ...533 Troubleshooting ...
Страница 564: ...Technical Specification 550 11 3 External Dimensions IP 20 Type 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Страница 585: ...Technical Specification 571 ...
Страница 594: ...580 ...
Страница 595: ...581 ...
Страница 596: ...582 ...