Code and
Features
Description
at 30 Hz, the time required to reach 30 Hz therefore is 2.5 seconds.
bA.09 Time
scale
Use the time scale for all time-related values. It is particularly useful
when a more accurate Acc/Dec times are required because of load
characteristics, or when the maximum time range needs to be
extended.
Configuration
Function
0
0.01sec
Sets 0.01 second as the minimum unit.
1
0.1sec
Sets 0.1 second as the minimum unit.
2
1sec
Sets 1 second as the minimum unit.
Note that the range of maximum time values may change automatically when the units are
changed. If for example, the acceleration time is set at 6000 seconds, a time scale change
from 1 second to 0.01 second will result in a modified acceleration time of 60.00 seconds.
4.8.2 Acc/Dec Time Based on Operation Frequency
Acc/Dec times can be set based on the time required to reach the next step frequency
from the existing operation frequency. To set the Acc/Dec time values based on the
existing operation frequency, set bA. 08 (acc/dec reference) in the Basic group to 1
(Delta Freq).
Group
Code
Name
Setting
Setting Range
Unit
Operatio
n
ACC Acceleration time
5.0
0.0
–600.0
sec
dEC Deceleration time
10.0
0.0
–600.0
sec
bA
08
Acc/Dec reference
frequency
1
Delta Freq
0
–1
-
Содержание G100
Страница 14: ......
Страница 16: ...5 5 7 5 kW 3 Phase ...
Страница 32: ...0 4 0 8 kW 1 5 2 2 kW 4 0 kW ...
Страница 48: ......
Страница 68: ......
Страница 81: ......
Страница 100: ......
Страница 116: ...trips automatic Reset Restart is not attempted and the Fire Mode Count is not increased ...
Страница 118: ......
Страница 130: ... Terminal connections for 3 wire operation 3 wire operation ...
Страница 140: ... PID control block diagram ...
Страница 165: ...Code and Features Description Code Description continuous rating ...
Страница 170: ......
Страница 186: ... Displayed as on the Keypad ...
Страница 200: ...provided signal output at 150 36 sec ...
Страница 216: ...Code and Features Description delay time delay time ...
Страница 219: ......
Страница 237: ......
Страница 253: ......
Страница 295: ......
Страница 314: ......
Страница 330: ...11 10 Remote Keypad Option It is comprised of a remote keypad and cables 1 m 2 m 3 m and 5 m Units mm ...
Страница 335: ...Manual Revision History Revision History No Date Edition Changes 1 2019 01 First Release ...