Take caution on any safety accidents when operating the inverter with Automatic
Restart After Reset enabled as the motor will begin rotating as soon as the inverter is
reset from the terminal block or keypad after a trip occurs.
4.8 Setting Acceleration and Deceleration Times
4.8.1 Acc/Dec Time Based on Maximum Frequency
Acc/Dec time values can be set based on maximum frequency, not on inverter
operation frequency. To set Acc/Dec time values based on maximum frequency, set
bA. 08 (Acc/Dec reference) in the Basic group to 0 (Max Freq).
Acceleration time set at the ACC (acceleration time) code in the Operation group
(dr.03) refers to the time required for the inverter to reach the maximum frequency
from a stopped (0 Hz) state. Likewise, the value set at the DEC (deceleration time)
code in the Operation group (dr.04) refers to the time required to return to a stopped
state (0 Hz) from the maximum frequency.
Group
Code
Name
Setting
Setting Range
Unit
Operation
ACC Acceleration time
5.0
0.0
–600.0
sec
dEC Deceleration time
10.0
0.0
–600.0
sec
dr
20 Maximum frequency
60.00
40.00
–400.00
Hz
bA
08
Acc/Dec reference
frequency
0
Max Freq
0
–1
-
09 Time scale setting
1
0.1sec
0
–2
-
Acc/Dec Time Based on Maximum Frequency
– Setting Details
Code and
Features
Description
bA.08
Ramp T Mode
Set the parameter value to 0 (Max Freq) to setup Acc/Dec time based
on maximum frequency.
Configuration
Function
0
Max Freq
Set the Acc/Dec time based on maximum
frequency.
1
Delta Freq
Set the Acc/Dec time based on operating
frequency.
If, for example, maximum frequency is 60.00 Hz, the Acc/Dec times
are set to 5 seconds, and the frequency reference for operation is set
Содержание G100
Страница 14: ......
Страница 16: ...5 5 7 5 kW 3 Phase ...
Страница 32: ...0 4 0 8 kW 1 5 2 2 kW 4 0 kW ...
Страница 48: ......
Страница 68: ......
Страница 81: ......
Страница 100: ......
Страница 116: ...trips automatic Reset Restart is not attempted and the Fire Mode Count is not increased ...
Страница 118: ......
Страница 130: ... Terminal connections for 3 wire operation 3 wire operation ...
Страница 140: ... PID control block diagram ...
Страница 165: ...Code and Features Description Code Description continuous rating ...
Страница 170: ......
Страница 186: ... Displayed as on the Keypad ...
Страница 200: ...provided signal output at 150 36 sec ...
Страница 216: ...Code and Features Description delay time delay time ...
Страница 219: ......
Страница 237: ......
Страница 253: ......
Страница 295: ......
Страница 314: ......
Страница 330: ...11 10 Remote Keypad Option It is comprised of a remote keypad and cables 1 m 2 m 3 m and 5 m Units mm ...
Страница 335: ...Manual Revision History Revision History No Date Edition Changes 1 2019 01 First Release ...