Forward/Reverse Run Prevention Setting Details
Code and
Features
Description
Ad.09 Run
Prevent
Choose a direction to prevent.
Configuration
Function
0
None
Do not set run prevention.
1
Forward Prev
Set forward run prevention.
2
Reverse Prev
Set reverse run prevention.
4.6 Power-on Run
When the Power-on Run command is enabled and the terminal block operation
command is ON for when there is a power supply to the inverter, it is started
immediately. To enable power-on run set the drv (command source) code to 1 (Fx/Rx-
1) or 2 (Fx/Rx-2) in the Operation group.
Group
Cod
e
Name
Setting
Setting
Range
Unit
Operatio
n
drv Command Source
1,
2
Fx/Rx-1 or
Fx/Rx-2
0
–4
-
Ad
10
Starting with power
on
1
Yes
0
–1
-
Note
•
A fault trip may be triggered if the inverter starts operation while a motor’s load (fan-
type load) is in free-run state. To prevent this from happening, set bit4 to 1 in Cn.71
(speed search options) of the Control group. The inverter will perform a speed search
at the beginning of the operation.
•
If the speed search is not enabled, the inverter will begin its operation in a normal V/F
pattern and accelerate the motor. If the inverter has been turned on without power-on
run enabled, the terminal block command must first be turned off, and then turned on
again to begin the inverter’s operation.
Содержание G100
Страница 14: ......
Страница 16: ...5 5 7 5 kW 3 Phase ...
Страница 32: ...0 4 0 8 kW 1 5 2 2 kW 4 0 kW ...
Страница 48: ......
Страница 68: ......
Страница 81: ......
Страница 100: ......
Страница 116: ...trips automatic Reset Restart is not attempted and the Fire Mode Count is not increased ...
Страница 118: ......
Страница 130: ... Terminal connections for 3 wire operation 3 wire operation ...
Страница 140: ... PID control block diagram ...
Страница 165: ...Code and Features Description Code Description continuous rating ...
Страница 170: ......
Страница 186: ... Displayed as on the Keypad ...
Страница 200: ...provided signal output at 150 36 sec ...
Страница 216: ...Code and Features Description delay time delay time ...
Страница 219: ......
Страница 237: ......
Страница 253: ......
Страница 295: ......
Страница 314: ......
Страница 330: ...11 10 Remote Keypad Option It is comprised of a remote keypad and cables 1 m 2 m 3 m and 5 m Units mm ...
Страница 335: ...Manual Revision History Revision History No Date Edition Changes 1 2019 01 First Release ...