11.8 Continuous Rated Current Derating
Carrier Frequency
The continuous rated current of the inverter is limited based on the carrier frequency.
Refer to the following graph.
Carrier
frequency
(kHz)
Continuous rated current
0.4~2.2kW
4.0kW
5.5kW
7.5kW
200V
400V
200V
400V
200V
400V
200V
400V
1~4
100%
100%
100%
100%
100%
100%
100%
100%
6
100%
100%
93%
100%
93%
93%
91%
89%
9
91%
91%
83%
85%
83%
83%
79%
72%
12
81%
81%
73%
70%
73%
73%
69%
59%
15
72%
72%
62%
58%
62%
62%
58%
48%
Содержание G100
Страница 14: ......
Страница 16: ...5 5 7 5 kW 3 Phase ...
Страница 32: ...0 4 0 8 kW 1 5 2 2 kW 4 0 kW ...
Страница 48: ......
Страница 68: ......
Страница 81: ......
Страница 100: ......
Страница 116: ...trips automatic Reset Restart is not attempted and the Fire Mode Count is not increased ...
Страница 118: ......
Страница 130: ... Terminal connections for 3 wire operation 3 wire operation ...
Страница 140: ... PID control block diagram ...
Страница 165: ...Code and Features Description Code Description continuous rating ...
Страница 170: ......
Страница 186: ... Displayed as on the Keypad ...
Страница 200: ...provided signal output at 150 36 sec ...
Страница 216: ...Code and Features Description delay time delay time ...
Страница 219: ......
Страница 237: ......
Страница 253: ......
Страница 295: ......
Страница 314: ......
Страница 330: ...11 10 Remote Keypad Option It is comprised of a remote keypad and cables 1 m 2 m 3 m and 5 m Units mm ...
Страница 335: ...Manual Revision History Revision History No Date Edition Changes 1 2019 01 First Release ...